Unit installation

Daikin IM 1089 Page 49
Figure 4: Thermostat TB155 autochangeover to be used with On-Off 24V valve packages, SPDT ACO and unit-mounted
Low Voltage Interface Board
Figure 5: Automatic changeover switch
(SPDT ACO Kit P/N 039398600)
Connect a wire from thermostat terminal TB2- 24
( Low fan speed) to the Low terminal
Remove Jumper JP1 to allow the remote mounte
d
10K Return Air Sensor to operate.
M
ount the 10K Return Air Sensor (PN 107345501) above the
filter through the knockout provid
ed
Note: (1) If a fan coil unit is to be used for heating or cooling
only, the SPDT ACO Switch (SPDT ACO Kit P/N
039398600) is not required. For such applications just
follow Step 2.
Four-pipe system (Cooling and Heating)
Two piping packages will be required for CW and HW coils.
The following accessories needed for field-installed thermostat
model T*155 (unit-mounted or wall-mounted):
Thermostat TA155 (kit) – PN 107345302 or Thermost
at
TB1
55 (kit) – PN 107345304
10K Return Air Sensor - PN 107345501 for unit-mounted
applications only (for wall-mounted applications the sen-
sor is imbedded with the thermostat)
Step 1: Installing valve packages
Solder the appropriate inlet and outlet CW pipe connectio
ns
from the valve package to the
coil connections.
Solder the appropriate inlet and outlet HW pipe connections
from the valve package to the coil connections.
Snap-on the Quick-connects of the valve actuators to the
a
ppropriate terminals of the Low Voltage Interface
Board as
p
er Fig. 2.
Step 2: Provide power to thermostat
(refer to Fig. 2 and 4)
Connect a wire from thermostat terminal TB1- 4 (L2 Neutral)
to the common terminal on the interface board (terminal C)
Connect a wire from thermostat terminal TB2- 1 (24VAC) to
the 24 V terminal connection R.
Connect fan speed wires from the ther
mostat to the
a
ppropriate Low Voltage Interface Board terminals:
Connect a wire from thermostat terminal TB2- 2
( High
fa
n speed) to the HI te
rminal
Connect a wire from thermostat terminal TB2- 3
( Med
fan speed) to the Med terminal
Connect a wire from thermostat terminal TB2- 24 ( Low
fa
n speed) to the Low terminal
Remove Jumper JP1 to allow the remote mounted th
e
10K Return Air Sensor to operate.
Mount the 10K Return Air Sensor (PN 107345501) above the
filter through the knockout provid
ed
Note: (2) For thermostats supplied by others refer to the
manufacturer’s installation literature and use this manual
as a guideline only.