Data Sheet

5.Current Sharing
File Name:CSP-3000-SPEC 2021-09-03
3000W Power Supply with Single Output
CSP-3000 serie s
CSP-3000 has the built-in active current sharing function and can be connected in parallel, up to 3 units, to provide higher output power as exhibited below :
Difference of output voltages among parallel units should be less than 0.2V(Can Fine tune by SVR1).
The total output current must not exceed the value determined by the following equation:
Maximum output current at parallel operation=(Rated current per unit)×(Number of unit)×0.9
The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
When out current<( 50% rate current)×(Number of unit),
the current shared among units may not be fully balanced.
CS+/CS- on CN1 are connected mutually in parallel(Note:CS+/CS- do not reverse connection).
Under parallel operation, the "PV/PC" function is not available.
No.1(Master)
No.2(Slave)
No.3(Slave)
Load
+V
-V
-V
-V
-V
+V
+V
+V
Output Voltage ADJ(SVR1)
max.
Current Sharing condition