Data Sheet
SPECIFICATION - Charger System
File Name:DHP-1U RACK SYSTEM-SPEC 2019-03-22
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Derating may be needed under low input voltages. Please check the static characteristics for more details.
3. Output of all the DBR-3200 modules are connected in parallel in the rack.
4. The equivalent leakage current of the system is determined by the quantity of populated chargers.
5. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.21000 1300 For guidance on how
to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
DHB-12K1U -24 DHB-12K1U -48
MODEL
VOLTAGE RANGE
Note.2
CHARGER
CURRENT RANGE
FREQUENCY RANGE
AC CURRENT (Typ.) per CHARGER
INPUT
OUTPUT
LEAKAGE CURRENT
per CHARGER
90 ~ 264VAC 127 ~ 370VDC
0 ~ 220A
DBR-3200-24 DBR-3200-48
47 ~ 63Hz
<1.5mA / 230VAC
17A/230VAC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
DIMENSION
PACKING
OTHERS
-30 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Rack 400*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket)
ENVIRONMENT
5.5Kg; 3pcs/17.5Kg/2.11CUFT
ALARM SIGNAL
REMOTE ON-OFF CONTROL
The isolated TTL signal out, Please refer to Installation Manual
By electrical signal or dry contact ON:short OFF:open
FUNCTION
SAFETY &
EMC
(Note 5)
0 ~ 440A
DHP-1U Rack System
3200~12800W 1U Distributed Power/Charger System
OUTPUT VOLTAGE PROGRAMMABLE(PV)
OUTPUT CURRENT
PROGRAMMABLE(PC)
Adjustment of output voltage is allowable to 75 ~ 125% of nominal output voltage. Please refer to the Function Manual.
Adjustment of output current is allowable to 20 ~ 100% of rated current. Please refer to the Function Manual.
28.8V
27.6V
57.6V
55.2V
BOOST CHARGE VOLTAGE(Vboost)(default)
FLOAT CHARGE VOLTAGE(Vfloat)(default)
TEMPERATURE COMPENSATION
-3mV / / cell / (24V = 12 cells ; 48V = 24 cells)℃
SAFETY STANDARDS
WITHSTAND VOLTAGE
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:700VDC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (E 50082-2), lev , criteria ANelHeavy industry
Compliance to EN55032 (CISPR32) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
EMC IMMUNITY
EMC EMISSION
AUXILIARY POWER
5V @ 0.3A, tolerance 10%, ripple 150mVp-p, 12V @ 0.8A, tolerance 10%, ripple 450mVp-p±±
Note.4