Datasheet

SPECIFICATION
DR-15-5 DR-15-12 DR-15-15 DR-15-24
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
SAFETY STANDARDS
WORKINGHUMIDITY
WORKINGTEMP.
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD Note.5
OVERVOLTAGE
5V 12V 15V 24V
2.4A 1.25A 1A 0.63A
0~2.4A 0~1.25A 0~1A 0~0.63A
12W 15W 15W 15.2W
80mVp-p 120mVp-p 120mVp-p
13.5~16.5V
150mVp-p
21.6~26.4V
2.0% 1.0% 1.0% 1.0%
10.8~13.2V4.75~5.5V
1.0% 1.0% 1.0% 1.0%
1.0% 1.0% 1.0% 1.0%
1000ms,50ms/230VAC1000ms,50ms/115VAC atfullload
70ms/230VAC16ms/115VAC atfullload
85~264VAC120~370VDC
47~63Hz
77% 84% 83.5% 85%
0.88A/115VAC0.48A/230VAC
COLDSTART 35A/115VAC65A/230VAC
105~160% ratedoutputpower
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
5.75~6.75V
Protectiontype: Shutoffo/pvoltage,clampingbyzenerdiode
13.8~16.2V 17.25~20.25V 27.6~32.4V
-20~+60 (Referto"DeratingCurve")
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
10~500Hz,2G10min./1cycle,periodfor60min. eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-6
1172.3Khrsmin.MIL-HDBK-217F(25 )
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Constant current operation region is within 60% ~100% rated output voltage. Protection type for short circuit is hiccup mode and will recover automatically
after fault condition is removed.
FileName:DR-15-SPEC2011-06-17
UL60950-1, TUVEN60950-1a EN50178pproved,designreferto
CompliancetoEN55011,EN55022(CISPR22),EN61204-3ClassB, EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2,EN61204-3,heavyindustrylevel,criteria A
15WSingleOutputIndustrialDINRailPowerSupply
DR-15 se ri es
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVAC
I/P-O/P:100MOhms/500VDC /25 /70%RH
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class
LED indicator for power on
100% full load burn-in test
3 years warranty
No load power consumption<0.5W
Features :
25*93*56mm(W*H*D)
0.1Kg;140pcs/15Kg/0.92CUFT
EMCIMMUNITY
EMCEMISSION