Datasheet
..
‧
‧
‧
‧
‧
‧
‧
‧
‧
• ℃
•
SPECIFICATION
HRP-75-3.3 HRP-75-5 HRP-75-7.5 HRP-75-12 HRP-75-15 HRP-75-24 HRP-75-36 HRP-75-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.) Note.2
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE (OPTIONAL)
SAFETY STANDARDS
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
3.3V 5V 7.5V 12V 15V 24V 36V 48V
15A
15A 10A 6.3A 5A 3.2A 2.1A 1.6A
0 ~ 15A 0 ~ 15A 0 ~ 10A 0 ~ 6.3A 0 ~ 5A 0 ~ 3.2A 0 ~ 2.1A 0 ~ 1.6A
49.5W 75W 75W 75.6W 75W 76.8W 75.6W 76.8W
80mVp-p 80mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 200mVp-p 240mVp-p
3.1 ~ 3.8V 4.7 ~ 5.8V 7.1 ~ 9V 11 ~ 13.8V 14.2 ~ 18V 21.6 ~ 28.8V 32 ~ 39.6V 45 ~ 55.2V
±2.5% ±2.5% ±2.5% ±1.5% ±1.5% ±1.5% ±1.5% ±1.5%
±1.0% ±1.0% ±1.0% ±0.3% ±0.3% ±0.2% ±0.2% ±0.2%
±2.0% ±2.0% ±1.5% ±1.0% ±0.5% ±0.5% ±0.5% ±0.5%
1800ms, 25ms/230VAC 1800ms, 25ms/115VAC at full load
50ms/230VAC 20ms/115VAC at full load
85 ~ 264VAC 120 ~ 370VDC
47 ~ 63Hz
PF>0.9/230VAC PF>0.95/115VAC at full load
77% 82.5%
6 ~ 7V 9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V 41.4 ~ 48.6V 57.6 ~ 67.2V
84% 87% 88% 88.5% 89% 89%
0.9A/115VAC 0.5A/230VAC
35A/115VAC 65A/230VAC
<1mA / 240VAC
105 ~ 135% rated output power
3.96 ~ 4.62V
Protection type : Constant current limiting, switch to hiccup mode for Vo<50% of rated voltage, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
UL60950-1, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024 , heavy industry level, criteria A, EN61000-6-2
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
-40 ~ +70℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03%/℃ (0 ~ 50℃)
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
394.8K hrs min. MIL-HDBK-217F (25℃)
129*98*38mm (L*W*H)
0.47Kg; 30pcs/ 15Kg/ 0.97CUFT
■
℃
HRP-75 series
75W Single Output with PFC Function
REMOTE CONTROL
RC+ / RC-: 0 ~ 0.8V = power on ; 4 ~ 10V = power off
FUNCTION
EMC IMMUNITY
EMC EMISSION
File Name:HRP-75-SPEC 2014-07-07