Datasheet

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT Note.6
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE Note.5
AC CURRENT (Typ.)
1800ms, 20ms/230VAC 1800ms, 20ms/115VAC at full load
100ms/230VAC 24ms/115VAC at full load
85 ~ 264VAC 120 ~ 370VDC
47 ~ 440Hz
74% 66%
13.8 ~ 16.2V
79%
17.25 ~ 20.25V
79%
27.6 ~ 32.4V
0.25A/115VAC 0.15A/230VAC
COLD START 25A/115VAC 45A/230VAC
Above 105% rated output power
5.75 ~ 6.75V3.8 ~ 4.95V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
I/P-O/P:4KVAC
I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH
20 ~ 90% RH non-condensing
-20 ~ +70 (Refer to "Derating Curve")
-40 ~ +85, 10 ~ 95% RH
±0.03%/ (0 ~ 50)
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
723.2Khrs min. MIL-HDBK-217F (25)
65*45*22mm (L*W*H)
0.045Kg; 120pcs/6.4Kg/0.97CUFT
File Name:NFM-10-SPEC 2017-07-14
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±1.0%
±1.0%
±1.0%
±1.0%
150mVp-p150mVp-p 150mVp-p 150mVp-p 240mVp-p
5V3.3V 15V
2A2.5A 0.67A 0.42A
0 ~ 2A0 ~ 2.5A 0 ~ 0.85A 0 ~ 0.67A 0 ~ 0.42A
10W8.25W 10.2W 10.05W 10.08W
NFM-10-5 NFM-10-12 NFM-10-15 NFM-10-24NFM-10-3.3
SAFETY STANDARDS
10W Output Switching Power Supply
NFM-10 series

RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3







 
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
Tj 140 typically (U1) detect on main control IC
Protection type : Shut off o/p voltage, clamping by zener diode
10.8 ~ 13.2V 13.5 ~ 16.5V 21.6 ~ 26.4V4.5 ~ 5.5V3 ~ 3.63V
Compliance to EN55011(CISPR11), EN55032 (CISPR32) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, EN61204-3, medical level, criteria A
ANSI/AAMI ES60601-1,TUV EN60601-1, IEC60601-1 approved












±2.0%
±2.0%
±1.0% ±1.0%
78%
12V
0.85A
±1.0%
24V
EMC IMMUNITY
EMC EMISSION
Touch current < 80 A/264VAC
μ
ISOLATION LEVEL
Primary-Secondary: 2xMOPP

Summary of content (2 pages)