Datasheet

Controlled by microprocessor
2/3/8 stage charging selectable on output panel (Note 4)
Universal AC input / Full range
Built-in active PFC function PF>0.95
Protection: Reverse Polarity / Short circuit / Over voltage / Over temperature
Charger for lead-acid batteries
3 color LED loading indicator
Built-in remote ON-OFF control
2-Bank charger
Temperature compensation function
FAN on/off control (depends on charging current)
3 years warranty
Features :
SPECIFICATION
PB-1000-12 PB-1000-24 PB-1000-48
MODEL
BOOST CHARGE VOLTAGE
FLOAT CHARGE VOLTAGE
BATTERY TYPE
LEAKAGE CURRENT FROM
BATTERY
(Typ.)
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)
(Note 3)
OUTPUT
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SHORT CIRCUIT
REVERSE POLARITY
SAFETY STANDARDS
SAFETY &
EMC
(Note 2)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
14.4V 28.8V 57.6V
13.8V
Open & Sealed Lead Acid
<1mA
200 ~ 600Ah
27.6V 55.2V
34.7A 17.4A
120 ~ 350Ah 60 ~ 175Ah
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
85% 88% 89%
12A/115VAC 5.2A/230VAC
25A/115VAC 50A/230VAC
<3.5mA / 240VAC
16 ~ 18V 32 ~ 35V 64.5 ~ 69.5V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
YES, protected by internal circuit
YES, protected by internal circuit
UL60950-1, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22), EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ 0.05%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
MTBF
127.4K hrs min. MIL-HDBK-217F (25 )
300*184*70mm(L*W*H)
DIMENSIONOTHERS
NOTE
PACKING
3.5Kg; 4pcs/15Kg/1.83CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
3. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
4. Please choose the "3 stage" selection when the charger is used to charge the batteries and power the loads in the same time.
PB-1000 series
1000W Intelligent Single Output Battery Charger
FUNCTION
REMOTE CONTROL
BATTER BANKS
FAST CHARGE
OUTPUT OK
TEMPERATURE COMPENSATION
CHARGER OK
Open: Normal work Short: Stop Charging
2 banks (A & B)
2 / 3 / 8 stage selectable
Relay contact rating(max.): 30V/1A resistive ; "Short" when the battery is full, "Open" when the battery is still charging
Relay contact rating(max.): 30V/1A resistive ; "Short" when the unit is working properly, "Open"when the unit is failure or the protection function is activating
By NTC, compensate both banks at the same time
File Name:PB-1000-SPEC 2015-06-09
..
OUTPUT CURRENT
60A
POWER FACTOR (Typ.) 0.95/230VAC 0.98/115VAC at full load
EMC IMMUNITY
EMC EMISSION

Summary of content (5 pages)