PB-1000 Instruction Manual
PB-1000 Instruction Manual 1.Main Specifications .. MODEL OUTPUT PB-1000-12 PB-1000-24 PB-1000-48 BOOST CHARGE VOLTAGE 14.4V 28.8V 57.6V FLOAT CHARGE VOLTAGE 13.8V 27.6V 55.2V OUTPUT CURRENT 60A 34.7A 17.4A 200 ~ 600Ah 120 ~ 350Ah 60 ~ 175Ah 88% 89% RECOMMENDED BATTERY CAPACITY(AMP HOURS)(Note 3) BATTERY TYPE LEAKAGE CURRENT FROM BATTERY (Typ.) INPUT Open & Sealed Lead Acid <1mA VOLTAGE RANGE 90 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 85% POWER FACTOR (Typ.) 0.
2.Front and back panel AC INLET ON/OFF SWITCH ON Fan Ventilation Hole OFF AC INPUT Figure 2.1 Front Panel Battery B Positive LED Indicator 2/8 stage selection switch Function Connector 1 3 5 7 9 2 4 6 8 10 Common Negative A { B B 8 Stage 1 3 5 7 9 Battery A Positive A 2 Stage 2 4 6 8 10 + - Battery B + - Battery A WARNING : Please check battery polarity before connection Figure 2.2 Back Panel Assembly Guidelines: 1.The charger should be turned OFF prior to battery connection.
3.Derating Curves 3.1 Charging current VS Temperature 100 80 LOAD (%) 60 40 20 -20 0 10 20 30 40 50 60 70 (HORIZONTAL) AMBIENT TEMPERATURE ( ) 4.Function Description of CN100 Pin No. Function Description 1,2 RY13 3,4 RY14 5,6 RY15 Relay contact rating(max.) : 30V/1A resistive. ; "Short" when the battery A is full, "Open" when the battery A is still charging. Relay contact rating(max.) : 30V/1A resistive. ; "Short" when the battery B is full, "Open" when the battery B is still charging.
Start V boost Charge Voltage 100% 10% Charge Current stage 1 stage 2 Constant Current Constant Voltage Battery Full Orange Color of LED Green State PB-1000-12 PB-1000-24 PB-1000-48 V boost 14.4V 28.8V 57.6V Constant Current 60A 34.7A 17.4A Figure 6.1 2 Stage Charging Curve 6.2 "8" stage charging (Selection switch to "8" stage) Advantage of pulse stage: Use pulse current to revive aged battery. Advantage of recond stage: Allow full charge of battery.
7.Function description 7.1 Remote Control The charger can be turned ON/OFF by using the "Remote Control" function. CN100 Between RC+(pin10) and RC-(pin9) 1 RY13 RY13 2 A Charger B B SW Open ON SW Short OFF 8 Stage 1 3 5 7 9 A RY14 RY14 2 Stage RY15 RY15 2 4 6 8 10 GND RTH 9 + + - Battery B - RC- RC+ 10 SW Battery A 7.2 Two Battery Banks The charger may be hooked up two battery banks (A and/or B). Connect the battery bank(s) as below.
CN100 7.4 Charger OK Relay(RY15) 1 RY13 RY13 2 Between pin5 and pin6 Charger RY14 RY14 Normal work ON (Short) Failure or the protection function is activating OFF(Open) RY15 RY15 GND RTH 7.5 Output OK Relay(RY13 & RY14) 9 RC- RC+ 10 1.Bank A OK (RY13) RY15 Between pin1 and pin2 Bank A Color of LED A CN100 1 Battery A Full ON (Short) Green Charging OFF(Open) Orange RY13 RY13 2 RY14 RY14 2.
9.Suggested battery capacity Model Battery capacity PB-1000-12 200-600AH PB-1000-24 120-350AH PB-1000-48 60-175AH Note:1.Using battery capacity larger than the suggested value will not lead to damage of battery. The only drawback is it may take longer to fully charge the battery. 2.If you're unsure about max allowable charging current of the battery, please refer to the battery's technical specification or consult its manufacturer. 10.Series and parallel connection of batteries 1.