10.Series and parallel connection of batteries
1.Batteries in series
Voltage can be doubled when 2 batteries are connected in series. However, the
capacity (Ah) will remain the same. For example, 2 x 12V 100Ah batteries connected
in series = 24V 100Ah.
++
BatteryBattery
--
9.Suggested battery capacity
Note: 1.Using battery capacity larger than the suggested value will not lead to damage
of the battery. The main drawback is it may take longer to fully charge the
battery.
2.If you're unsure about max allowable charging current of your battery, please
refer to the battery's technical specification or consult its manufacturer.
Model
PB-600-12 135-400AH
PB-600-24
PB-600-48
70-210AH
35-105AH
Battery capacity
8.Wiring for battery
Select suitable wire guage based on rated charging current. Refer to the following
table for minimum wire gauge. We highly recommend using RED wire for + connection
and BLACK wire for-connection:
AWG
14 2.1 12
12 3.3 22
10 5.3 35
7 10 46
6 16 60
4 25 80
CROSS SECTION(mm )
2
Max. Current(A)
UL1015(600V 105 )