Data Sheet
SPECIFICATION
File Name:PSPA-1000-SPEC 2018-10-04
1000W with PFC and Parallel Function
PSPA-1000 series
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY(Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
1000ms,50ms/115VAC 1000ms,50ms/230VAC
16ms at full load
90 ~ 264VAC(300VAC for 5 sec.) 127 ~ 370VDC
47 ~ 63Hz
92% 93% 93.5%
8.5A/115VAC 5A/230VAC
20A/115VAC 40A/230VAC
<0.5mA/240VAC
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
UL62368-1, TUV EN62368-1 EAC TP TC 004 approved
,,BSMI CNS14336-1
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
non-condensing
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
274.3K hrs min. Telcordia SR-332 (Bellcore) ; 94.4K hrs min. MIL-HDBK-217F (25 )℃
170*120*93mm (L*W*H)
12V 15V 24V
80A 64A 42A 21A
0 ~ 80A 0 ~ 64A 0 ~ 42A 0 ~ 21A
960W 960W 1008W 1008W
150mVp-p 150mVp-p 200mVp-p 250mVp-p
11 ~ 14V 14 ~ 17V 22 ~ 28V 46 ~ 56V
±2.0% ±1.5% ±1.0% ±1.0%
±2.0%
±0.5%
±1.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
PSPA-1000-12 PSPA-1000-15 PSPA-1000-24 PSPA-1000-48
1.93Kg ; 8pcs/16.4Kg/1.53CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the derating curve for more details.
5. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
OVER VOLTAGE
14.5 ~ 16.5V 18.2 ~ 20.6V 29 ~ 33V 58 ~ 65V
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
0.95/230VAC 0.99/115VAC at full load
SAFETY &
EMC
(Note 5)
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION
OVER TEMPERATURE
Shut down o/p voltage, re-power on to recover
94%
48V
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Class B
Class B
Class A
-----
EMC IMMUNITY
EMC EMISSION
EN55024, EN61000-6-2, BSMI CNS13438
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 4, 2KV/Line-Line 4KV/Line-Earth
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
CURRENT SHARING
Up to 4000W or (3+1) units. Please refer to the Function Manual.
POK SIGNAL
REMOTE ON-OFF CONTROL
Power ON : short; Power OFF : open. Please refer to the Function Manual.
The TTL signal out, PSU turn on = 2.4 ~ 5V ; PSU turn off = 0 ~ 0.4V. Please refer to the Function Manual.
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual.