Instruction Manual
SPECIFICATION
File Name:PSPA-1000-SPEC 2022-08-08
1000W with PFC and Parallel Function
PSPA-1000 series
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.4
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY(Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
1000ms,50ms/115VAC 1000ms,50ms/230VAC
16ms at full load
90 ~ 264VAC(300VAC for 5 sec.) 127 ~ 370VDC
47 ~ 63Hz
92% 93% 93.5%
8.5A/115VAC 5A/230VAC
20A/115VAC 40A/230VAC
<0.5mA/240VAC
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
UL62368-1, CAN/CSA C22.2 , TUV BS EN/EN62368-1, BSMI CNS14336-1, AS/NZS62368.1, EAC TP TC 004 approved No. 62368-1
-20 ~ +70℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH non-condensing
±0.03%/℃ (0 ~ 50℃)
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
807.1K hrs min. Telcordia SR-332 (Bellcore) ; 94.9K hrs min. MIL-HDBK-217F (25℃)
170*120*93mm (L*W*H)
12V 15V 24V
80A 64A 42A 21A
0 ~ 80A 0 ~ 64A 0 ~ 42A 0 ~ 21A
960W 960W 1008W 1008W
150mVp-p 150mVp-p 200mVp-p 250mVp-p
11 ~ 14V 14 ~ 17V 22 ~ 28V 46 ~ 56V
±2.0% ±1.5% ±1.0% ±1.0%
±2.0%
±0.5%
±1.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
PSPA-1000-12 PSPA-1000-15 PSPA-1000-24 PSPA-1000-48
1.93Kg ; 8pcs/16.4Kg/1.53CUFT
℃
http://www.meanwell.com)
℃ ℃
※ : https://www.meanwell.com/serviceDisclaimer.aspx
OVER VOLTAGE
14.5 ~ 16.5V 18.2 ~ 20.6V 29 ~ 33V 58 ~ 65V
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
ENVIRONMENT
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
0.95/230VAC 0.99/115VAC at full load
SAFETY &
EMC
(Note 5)
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION
OVER TEMPERATURE
Shut down o/p voltage, re-power on to recover
94%
48V
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
Standard
Standard
BS EN/EN55032 (CISPR32)
BS EN/EN55032 (CISPR32)
BS EN/EN61000-3-2
BS EN/EN61000-3-3
BS EN/EN61000-4-2
BS EN/EN61000-4-3
BS EN/EN61000-4-4
BS EN/EN61000-4-5
BS EN/EN61000-4-6
BS EN/EN61000-4-8
BS EN/EN61000-4-11
Test Level / Note
Test Level / Note
Class B
Class B
Class A
-----
EMC IMMUNITY
EMC EMISSION
BS EN/EN55035, BS EN/EN61000-6-2, BSMI CNS13438
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 4, 2KV/Line-Line 4KV/Line-Earth
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
CURRENT SHARING
Up to 4000W or (3+1) units. Please refer to the Function Manual.
POK SIGNAL
REMOTE ON-OFF CONTROL
Power ON : short; Power OFF : open. Please refer to the Function Manual.
The TTL signal out, PSU turn on = 2.4 ~ 5V ; PSU turn off = 0 ~ 0.4V. Please refer to the Function Manual.
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual.