File Name:PSPA-1000-SPEC 2022-08-08
1000W with PFC and Parallel Function
PSPA-1000 series
2.Remote ON-OFF Control
The power supply can be turned ON-OFF individually or along with other units by using the “Remote ON-OFF” function.
3.POK signal
POK signal indicates the output status of the power supply. It can operate in two ways : One is sinking current from external TTL signal ; the other is
sending out a TTL voltage signal.
Sinking current from external TTL signal: The maximum sink current is 10mA and the maximum external voltage is 5.6V.
4.Current Sharing with Remote Sense
Difference of output voltages among parallel units should be less than 0.2V.
PSPA-1000 has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below :
The total output current must not exceed the value determined by the following equation:
When the total output current is less than 5% of the total rated current, or say (5% of Rated current per unit)×(Number of unit)
the current shared among units may not be fully balanced.
Maximum output current at parallel operation=(Rated current per unit)×(Number of unit)×0.9
The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
Application
Circuit
For Remote Sense, please refer to “Remote Sense” section.
+V +V +V +V+V +V +V +V+V +V +V +V+V +V +V +V-V -V -V -V-V -V -V -V-V -V -V -V-V -V -V -V
RS+ RS+ RS+ RS+
RS- RS- RS- RS-
L L L LN N N NFG FG FG FGP P P P
POK POK POK POK
LOAD
-V +V
Between R.C. and R.C.G
Switch Short
Switch Open
Power Supply Status
ON
OFF
R.C.G R.C.G R.C.G R.C.G
R.C. R.C. R.C. R.C.
+V+V+V+V-V-V-V-V
RS+
RS-
LNFGP
POK
R.C.G
R.C.
switch
+V+V+V+V-V-V-V-V
RS+
RS-
LNFGP
POK
R.C.G
R.C.