Data Sheet
RCP-1000 series
1000W Front End Power System
File Name:RCP-1000-SPEC 2020-03-27
3.1 RCP-1000-12
90
92
94
96
98
100
Vout (%) Vout (%)
180K 240K 350K 560K 1.2M NC
R1 ( )Ω
min. 0.1W
R2 ( )Ω
min. 0.1W
100
102
104
106
108
110
NC 300K 120K 62K 31K 13K
※ In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 90~110% of the nominal voltage by applying
EXTERNAL RESISTANCE.
◎ +S & +V, -S & -V also need to be connected on CN501
3. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
3.3 RCP-1000-48
90
92
94
96
98
100
1.3M 1.7M 2.4M 3.6M 7.6M NC
100
102
104
106
108
110
NC 345K 140K 70K 36K 15K
3.2 RCP-1000-24
90
92
94
96
98
100
560K 750K 1M 1.6M 3.3M NC
100
102
104
106
108
110
NC 330K 130K 62K 30K 10K
Vout (%)
Vout (%)
Vout (%)
Vout (%)
R1 ( )Ω
min. 0.1W
R1 ( )Ω
min. 0.1W
R2 ( )Ω
min. 0.1W
R2 ( )Ω
min. 0.1W
4. I C Bus Interface
2
※ please refer to the Installation Manual.For the details of I C bus used on RCP-1000-C models,
2
+S
+V
RCP-1000 LOAD
8
-S
-V
13
9
R1
R2
V-TRIM
PIN8 +S
PIN 13 V-TRIM
PIN9 -S