Function Manual
1.1 Remote Sense
1. Voltage Drop Compensation
The Remote Sense compensates voltage drop on the load wiring up to 0.5V
-V
+V
RCP-2000
+S
-S
LOAD
-V
+V
14
15
Sense lines should be twisted in pairs
+V
-V
+S
-S
RCP-2000
14
15
PIN14 +S
PIN14 +S
PIN15 -S
PIN15 -S
PV
-S
-V
+V
+S
RCP-2000
11
15
14
0~5V
-V Signal
9
LOAD
2000W Rack Mountable Front End Rectifier
RCP-2000 series
File Name:RCP-2000-SPEC 2018-08-16
1.2 Local Sense
The +S,-S have to be connected to the ,-V , respectively, as the following diagram, in order to get the correct output voltage if Remote+V(signal) (signal)
Sense is not used.
In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 90~110% of the nominal voltage by applying
EXTERNAL VOLTAGE.
2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
PIN9 -V(signal)
PIN11 PV
+S & +V, -S & -V also need to be connected on CN501