Datasheet

SPECIFICATION
MODEL RPD-60A
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
Note.8
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
5V
5A
0.5 ~ 5.5A
49W
53.9W
80mVp-p
+3,-2%
±0.5%
±1.5%
300ms, 15ms/230VAC 300ms, 15ms/115VAC at full load
70ms/230VAC 14ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
CH1: 5.75 ~ 6.75V
78%
1.1A/115VAC 0.7 A/230VAC
COLD START 60A/230VAC 30A/115VAC
115 ~ 150% rated output power
-20 ~ +65 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ 0.03%/ (0 ~ 45 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
677.8K hrs min. MIL-HDBK-217F (25 )
101.6*50.8*29mm (L*W*H)
0.15Kg; 96pcs/15.4Kg/0.89CUFT
60W Dual Output Medical Type
RPD-60 series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
ENVIRONMENT
SAFETY &
EMC
(Note 5)
PROTECTION
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. 33% Duty cycle maximum within every 30 seconds. Average output power should not exceed the rated power.
5. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
6. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
7. Heat Sink HS1,HS2 can not be shorted.
8. Touch current was measured from primary input to DC output.
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
Features :
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
RPD-60B
12V
CH2
24V
CH2
5V
CH1
2A 1.5A3.5A
0.1 ~ 2.2A 0.1 ~ 1.65A0.5 ~ 3.85A
53.5W
58.85W
80mVp-p 100mVp-p80mVp-p
±6.0% +8,-4%
±1.0%
±2.0% ±2.0%
±1.0%
+3,-2%
±0.5%
±1.5%
82%
LINE REGULATION
LOAD REGULATION
CH1OUTPUT NUMBER
4" 2" miniature size×
Universal AC input/Full range
Low leakage current <100 A
Protections: Short circuit / Over load / Over voltage
Cooling by free air convection
Medical safety approved (2 x MOPP between primary to secondary)
UL60950-1/IEC60950-1/EN60950-1 ITE safety approved
Fixed switch frequency at 100KHz
Suitable for BF application with appropriate system consideration
3 years warranty
PEAK LOAD(10sec.) Note.4
File Name:RPD-60-SPEC 2015-08-06
UL60950-1, TUV EN60950-1, ANSI/AAMI ES60601-1, TUV EN60601-1, IEC60601-1 approved
Compliance to EN55011(CISPR11),EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, EN61204-3, medical level, criteria A
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMC IMMUNITY
EMC EMISSION
Earth leakage current < 150 A/264VAC , Touch current < 100 A/264VACμ
μ
μ
ISOLATION LEVEL
Primary-Secondary: 2xMOPP, Primary-Earth:1xMOPP, Secondary-Earth:1xMOPP
EN 60601-1
IEC 60601-1
8