Datasheet

SPECIFICATION
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT
VOLTAGE ADJ.RANGE
SETUP,RISETIME
HOLDTIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY(Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
SAFETY STANDARDS
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
500ms,30ms/230VAC500ms,30ms/115VACatfullload
100ms/230VAC20ms/115VACatfullload
90~264VAC127~370VDC
47~63Hz
1.5A/115VAC1A/230VAC
COLDSTART 25A/115VAC50A/230VAC
140~180% ratedoutputpower
-20~+70 (Refertooutputloadderatingcurve)
20~90%RH non-condensing
-40~+85 ,10~95%RH
0.03%/ (0~45 )
10~500Hz,2G10min./1cycle,periodfor 60min.eachalongX, Y,Zaxes
FileName:RPT-75-SPEC2006-12-18
OVERVOLTAGE
HARMONICCURRENT
EMSIMMUNITY
RPT- 7 5 se ri es
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
EMICONDUCTION&RADIATION
ENVIRONMENT
SAFETY &
EMC
(Note4)
PROTECTION
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Protectiontype: Hiccupmode,recoversautomaticallyafterfaultconditionisremoved
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
76%
LINEREGULATION
LOADREGULATION
CH1 CH1 CH1OUTPUTNUMBER
Features :
Universal AC input/Full range
Low leakage current<200uA
Protections:Short circuit/Over load/Over voltage
Free air convection for rated power and 23.5CFM forced air
convection for peak load
UL60601-1/IEC60601-1/EN60601-1 medical safety approved
Fixed switching frequency at 65KHz
3 years warranty
75W TripleOutputMedical Type
521.2Khrsmin.MIL-HDBK-217F(25 )
127*76.2*31mm(L*W*H)
CompliancetoEN55011(CISPR11),EN55022(CISPR22)ClassB
Complianceto EN61000-3-2,-3
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC
UL60601-1,TUVEN60601-1 Approved
I/P-O/P:4KVACI/P-FG:1.5KVACO/P-FG:1.5KVAC
PEAKLOAD(23.5CFM)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
0.26Kg;63pcs/17.4Kg/1.35CUFT
RPT-75A
5V
6A
0.6~8A
6A
0.6~8A
68.5W
93W
80mVp-p
CH1:4.75~5.5V
2.0%
0.5%
1.5%
RPT-75B RPT-75C
12V
CH2 CH2 CH2
-5V
CH3 CH3 CH3
12V -12V 15V -15V5V 5V
3A
0.2~4A
3A
0.2~4A
0.5A
0.1~1A
0.5A
0.1~1A
2.3A
0.1~3A
0.5A
0.1~1A
6A
0.6~8A
72W
100W
72W
100W
120mVp-p 120mVp-p 120mVp-p 120mVp-p 150mVp-p 150mVp-p80mVp-p 80mVp-p
6.0% 5.0% 6.0% 5.0% 8.0% 5.0%
1.0% 1.0% 1.0% 1.0% 1.0% 1.0%
3.0% 1.0% 3.0% 1.0% 3.0% 1.0%
2.0% 2.0%
0.5%
1.5%
0.5%
1.5%
77% 77%
CH1:5.75~6.75V
CompliancetoEN61000-4-2,3,4,5,6,8,11;ENV50204,EN55024,EN60601-1-2,EN61000-6-2,EN61204-3heavyindustrylevel,EN61204-3Medicallevel,criteria A
Earthleakagecurrent<200uA /264VAC,Patient <100uA/264VACleakagecurrent
EN60601-1
IEC60601-1

Summary of content (3 pages)