Data Sheet

Function Manual
1000W Power Supply with Single Output
RSP-1000 series
File Name:RSP-1000-SPEC 2020-03-27
1.Remote Sense
The Remote Sense compensates voltage drop on the load wiring up to 0.5V
The signal should be connected to the positive terminal of the load whereas signal to the negative terminal.+S -S
This configuration is based on the assumption the Output Voltage Programming is not activated and power supply is ON.
TB1
-V+V
CN50
1 11
2 12
PIN8 Vco
PIN10 Vca
PIN6 REMOTE ON-OFF
LOAD
-V
+V
PIN1 +S
PIN2 -S
Sense lines should be twisted in pairs to minimize noise pick-up.
Fig 1.1
Between andRemote ON-OFF (pin6) -S(pin2)
Switch Short
Switch Open
ON
Power Supply Status
OFF
2.Remote ON-OFF Control
When multiple power supplies need to turn ON/OFF simultaneously by Remote ON-OFF control, -S & -V, as well as +S & +V, on each power supply
should be connected.
TB1
-V+V
CN50
Fig 2.1
Fig 3.1
LOAD
-
+
1 11
2 12
Switch
PIN2 -S
PIN6 REMOTE ON-OFF
PIN10 Vca
PIN8 Vco
3.DC_OK signal
"DC_OK" is an open collector signal. It indicates the output status of the power supply. It can operate in two ways : One is sinking current from external
TTL signal ; the other is sending out a TTL voltage signal.
The maximum sink current is 10mAand the maximum external voltage is 5.6V.Sinking current from external TTL signal:
Sending out TTL voltage signal :
Between andDC- OK(pin5) GND(pin11&12)
0 ~ 1V
3.3 ~ 5.6V
Output Status
ON
OFF
TB1
-V+V
CN50
1 11
2 12
PIN2 -S
PIN5 DC_OK PIN12 GND
PIN6 REMOTE ON-OFF
PIN10 Vca
PIN8 Vco
The power supply can be turned ON-OFF indivicluaaly or along with other units by using the “Remote ON-OFF” function.
The power supply is shipped, by factory default, with and shorted by connector.Remote ON-OFF(pin6) -S(pin2)