5.Current Sharing with Remote Sensing
RSP-2000 has the built-in active current sharing function and can be connected in parallel to provide higher output power :
(1)Parallel operation is available by connecting the units shown as below.
(DA,DB and GND are connected mutually in parallel).
(2)Difference of output voltages among parallel units should be less than 0.2V.
(3)The total output current must not exceed the value determined by the following equation.
(4)In parallel operation 4 units is the maximum, please consult the manufacturer for applications of more connecting in parallel.
(5)The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
(6) Under parallel operation, the minimum output load should be greater than 5% of total output load.
(7) Under parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal ripple level once the
output load is more than 5%.
(8) CN502/CN504 Function pin connection
V is CN502/CN504 connected to plug pin, X is CN502/CN504 not connected to plug pin.
Parallel
CN502 CN502 CN502 CN502CN504 CN504 CN504 CN504
PSU1 PSU2 PSU3 PSU4
1 unit
X
X
X X
V
V VV
V V
V
V
V V
V
VV
V VV
2 unit
3 unit
4 unit
(output current at parallel operation)=(Rated current per unit) (Number of unit) 0.9× ×
DA DA DA DA
DA DA DA DA
DB DB DB DB
DB DB DB DB
GND GND GND GND
GND GND GND GND
PSU1
RSP-2000 RSP-2000 RSP-2000 RSP-2 000
PSU2 PSU3 PSU4
+V
If the lines of CN502 are too long, they should
be twisted i n pairs to avoid the no ise.
-V
LOAD
TB1 TB1 TB1 TB1
CN502 CN502 CN502 CN502
CN5 04 CN504 CN504 CN504
-V -V -V -V+V +V +V +V
1 1 1 1
2 2 2 2
5 5 5 5
6 6 6 6
3 3 3 31 1 1 15 5 5 5
PSU2 CN502 PSU3 CN502
PSU4 CN502PSU1 CN502
Fig 6. 1
2 2 2 24 4 4 46 6 6 6
2000W Single Output Power Supply
RSP -20 00
s eri es
File Nam e:RSP- 2000-SP EC 2014-03-04