Instructions

SPECIFICATION
RSP-2400-12
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
OUTPUT VOLTAGE
PROGRAMMABLE(PV)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD (OLP)
OVER VOLTAGE
AC CURRENT (Typ.)
12V
166.7A
0 ~ 166.7A
2000.4W
150mVp-p
10.8 ~ 13.2V
±1.0%
±0.5%
±0.5%
1000ms, 80ms at full load
12ms at full load
180 ~ 264VAC 254 ~ 370VDC
47 ~ 63Hz
88%
15.5A/180VAC 12A/230VAC
60A/230VAC
<2.0mA / 240VAC
100 ~ 112% rated output power
13.8 ~ 16.8V
User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
28.8 ~ 33.6V 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85, 10 ~ 95% RH non-condensing
±0.05%/ (0 ~ 50)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
234.1K hrs min. Telcordia SR-332 (Bellcore) ; 83.9K hrs min. MIL-HDBK-217F (25)
278*177.8*63.5mm (L*W*H)
3.3Kg; 4pcs/14.2Kg/1.81CUFT
90.5% 91.5%
±0.5% ±0.5%
±0.5% ±0.5%
±1.0% ±1.0%
150mVp-p
22 ~ 28V
200mVp-p
43 ~ 56V
24V
100A
0 ~ 100A
2400W
48V
50A
0 ~ 50A
2400W
RSP-2400-24 RSP-2400-48



  
    

  
Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
POWER FACTOR (Typ.) 0.95/230VAC at full load
SAFETY STANDARDS
UL62368-1, CSA C22.2 , TUV EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved No. 62368-1
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
2400W Power Supply with Single Output
RSP-2400 series
ALARM SIGNAL OUTPUT
REMOTE ON-OFF CONTROL
AUXILIARY POWER
Please refer to the Function Manual
Power OK signal. Please refer to the Function Manual
12V@0.1A(Only for Remote ON-OFF control)
Please refer to the Function Manual.
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.25V. Please refer to the Function Manual.
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2, BSMI CNS13438
Standard
Standard
EN55032 (CISPR32)
EN55032 (CISPR32)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class A
-----
-----
EMC IMMUNITY
EMC EMISSION
File Name:RSP-2400-SPEC 2020-09-29
4.8 ~ 28V 9.6 ~ 56V
2.4 ~ 13.2V
CURRENT SHARING
Up to 7200W or (2+1) units. Please refer to the Function Manual.
Level 3, 2KV/Line-Earth ; Level 2, 1KV/Line-Line