Data Sheet
1.Remote ON/OFF
(1)Remote ON/OFF control becomes available by applying voltage in CN51
(2)Table 1.1 shows the specification of Remote ON/OFF function
(3)Fig.1.2 shows the example to connect Remote ON/OFF control function
Table 1.1 Specification of Remote ON/OFF
Fig.1.2 Examples of connecting remote ON/OFF
Connection Method
SW Logic
Output on SW Open SW Open
SW Open
Fig. 1.2(A) Fig. 1.2(B) Fig. 1.2(C)
Output off SW Close SW Close
SW Close
2.2KΩ
AUX
RC1
12V typ.
AUXG
150Ω
RCG
RC2
SW
620Ω
5V
150Ω
RC2
12V typ.
RCG
AUXG
2.2KΩ
RC1
AUX
(A)Using external voltage source (B)Using internal 12V auxiliary output
SW
150Ω
RC2
12V typ.
AUXG
SW
RCG
(C)Using internal 12V auxiliary output
2.2KΩ
RC1
AUX
SD-1000 series
Function Description of CN51
Function Manual
Pin No. Function
Description
1
3
5
6
7
8
9
10
4
2
+S
O/P OK
AUX
AUXG
RC1
RC2
RCG
NC
GND
-S
Open collector signal, referenced to pin4(GND). Low when PSU turns on. The maximum sink current is 10mA and the maximum
external voltage is 13V.
Auxiliary voltage output, 10.8~13.2V referenced to pin6(AUXG).The maximum load current is 0.25A.
Auxiliary voltage output ground. The signal return is isolated from the output terminals(+V & -V).
Remote ON/OFF
Remote ON/OFF
Remote ON/OFF ground
No connection
These pins connect to the negative terminal (-V).
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
File Name:SD-1000-SPEC 2020-02-11
1000W Single Output DC-DC Converter