Data Sheet

240W Single Output with PFC Function
SP-240 series
Model: SP-240-24 Test Report 5 / 6
SAFETY TEST
NO TEST ITEM SPECIFICATION TEST CONDITION RESULT VERDICT
1 WITHSTAND VOLTAGE
I/P-O/P 3 KVAC/min
I/P-FG 1.5 KVAC/min
O/P-FG 0.5 KVAC/min
I/P-O/P 3.6 KVAC/min
I/P-FG 1.8 KVAC/min
O/P-FG 0.6 KVAC/min
Ta25
I/P-O/P
7.3 mA
P
I/P-FG
6.84
mA
O/P-FG
5.54 mA
NO DAMAGE
2 ISOLATION RESISTANCE
I/P-O/P500VDC>100M
I/P-FG 500VDC>100M
O/P-FG500VDC>100M
I/P-O/P 500 VDC
I/P-FG 500 VDC
O/P-FG 500 VDC
Ta25/70%RH
I/P-O/P
12
G
P
I/P-FG
3 G
O/P-FG
3.5
G
NO DAMAGE
3 GROUNDING CONTINUITY FG(PE) TO CHASSIS
OR TRACE < 100 m
40 A / 2min
Ta25 / 70%RH
8 m
P
4 APPROVAL
TUV Certificate NO R50159049
UL File NO E183223
P
E.M.C TEST
NO TEST ITEM SPECIFICATION TEST CONDITION RESULT VERDICT
1 HARMONIC EN61000-3-2
CLASS A
CLASS D
I/P 230 VAC/50HZ
O/PFULL LOAD
Ta25
PASS
P
2 CONDUCTION EN55022
CLASS B
I/P 230 VAC (50HZ)
O/PFULL/50% LOAD
Ta25
PASS
Test by certified Lab
P
3 RADIATION EN55022
CLASS B
I/P 230 VAC (50HZ)
O/PFULL LOAD
Ta25
PASS
Test by certified Lab
P
4 E.S.D EN61000-4-2
LIGHT INDUSTRY
AIR8KV / Contact4KV
I/P 230 VAC/50HZ
O/PFULL LOAD
Ta25
CRITERIA A
P
5 E.F.T EN61000-4-4
LIGHT INDUSTRY
INPUT 1KV
I/P 230 VAC/50HZ
O/PFULL LOAD
Ta25
CRITERIA A
P
6 SURGE IEC61000-4-5
LIGHT INDUSTRY
L-N 1KV
L,N-PE2KV
I/P 230 VAC/50HZ
O/PFULL LOAD
Ta25
CRITERIA A
P
7
Test by certified Lab Test Report Prepare
M.T.B.F & LIFE CYCLE CALCULATION
NO TEST ITEM SPECIFICATION TEST CONDITION RESULT VERDICT
1 CAPACITOR
LIFE CYCLE
SP-240-5SUPPOSE C103 IS THE MOST CRITICAL COMPONENT
I/P 230VAC O/PFULL LOAD Ta= 25 LIFE TIME=498365.4
I/P 230VAC O/PFULL LOAD Ta=40 LIFE TIME=249128.4
HRS
HRS
P
2 MTBF MIL-HDBK-217F NOTICES2 PARTS COUNT
TOTAL FAILURE RATE 284K HRS
P