User manual

16
Chassis
0 10 20 30 40 50 60 70
20
40
60
80
100
21VDC 23VDC 30VDC (HORIZONTAL)
20
40
60
80
100
(E)Derating
BatteryInputVoltage(V)-24VModel
LOAD(%)
LOAD(%)
Ambient Temperature( )
Figure7.2:OutputDeratingCurve Figure7.3:InputDeratingCurve
1.CompanyName:MeanWellEnterprisesCoLtd
2.ModelName:1GG1HS-191
3.Rating:150A
4. Torque:106.2Ib.inmax.
5.SuitableWire:Copperwire(temprating:75C)
6.IntendedforterminationontoaListedringtongueconnector
7. ToBeSoldOnlyWithInstallationInstructions
8. A mountingscrew thatisfirstinsertedthroughthetangandisthreaded
intotheconnectortosecuretheconnectortothetangshallbetorqued
to32in-lbsminimum
9.MountingScrews-PlatedSteel. Twoprovided,sizeM4
Cat.No.(1GG1HS-212)
WireRange(10-4 AWG
StrCuSolderedWires)
Torque(17.7-26.5inlb)
(F)NotesonOutputLoads:
TN/TS-1500 Series can power most of equipments t h a t need an AC
sourceof1500W.Butforcertainspecificty p eo fload,theunitmaynot
workproperly.
(1)Since inductive loads or motor based equipments need a large start up
(2)When the output are capacitive or rectified equipments (such as switching
current (6~10 times of its rated current), please make sure this start up
power supply), we suggest operating these equipment at no load or light
load condition. Increase the loads slightly only after the TN/TS-1500 has
starteduptoensureproperoperation.
currentislessthanthemaximumcurrentcapabilityoftheinverter.