User Instructions

Clog with foreign bodies R emove the foreign objects
Fan does
not s pin
Ma lfunction of the fan
Repair required. Please send it back
to us or any of our distributors
Short circuit protection
Make sure the output is no t
overloaded or short circui ted
Batteries are aged or broken Replace the b atteries
Discharging
perio d of
batte ries is
too s hort
Battery capacity is too small
Reconfirm the specificatio n and
enlarge the battery capacity as
suggested
Statu s Possible Reasons Ways to Eliminate
Abnormal input
Check the AC or DC input sources.
Make sure the voltage is within the
required range.
Ov er temperature
protection
Make sure that the ventilation is not
blocked or wh ether the ambient
temperature is too high. Please
derating the o utput usage or reduce
the ambient temperature.
Ov erload protection
Make sure the output load does not
exceed the rated value or the
instantaneous start up current is not
too high. (for inductive or capacitive
loads)
No AC output
volta ge
10
(1)Sinc e induct ive loads or motor based equipments ne ed a large s tart up
(2)When the output are capacitive or rectified equipments (such as sw itching
current (6~10 times of its rated current) , the inverter m ay n ot s tart up
succ essfully with these kinds of load.
power supply), it is suggested to operate these equipment at no load or light
load. To ensure proper operation, you should i ncrease the loads on ly after
TS-700/1000 has started up.
7. Failure Correction No tes
TS-70 0/1000 should be s erviced by a pro fessi ona l tec hni cian . An y improper
usage or modification may damage the unit or result in shock ha zard. If you are
not able to clear the failure condition, please contact Mean WEL L or any of our
distributors for repair service.
8. Warranty
Three years of global warranty is provided for TS-700/1000 under normal
opera ting conditi ons. Please do not change components or m odify the unit
by yo urs elf or MEAN WELL may reserve the right n ot to pr ovide t he
complete warranty.