User manual

4
Table4-1:LEDIndicationofOutputVoltage/FrequencyCombination
50Hz
60Hz
100Vac
Output
Voltage
Frequency
110Vac 115Vac 120Vac
(200Vac)
Status
Status
Light
Dark
Battery
Battery
Load
Load
Flashing
(220Vac) (230Vac) (240Vac)
Figure4.1: AdjustmentofOutputVoltage,Frequency,andSavingMode
Useaninsulatedstickto
pressthissettingbutton
Load
Battery
Status
ACOutput
Setting
OFF
ON
Remoteport
4.Setup(OutputVoltage,Frequency,andSavingMode)
4.1InitialState
4.2ProcedureofSettingupOutputVoltage,Frequency,andSavingMode
The initial state is 110Vac/60Hz or 230Vac/50Hz and the "Saving Mode" is
activated. If users need to revise it for certain application, it can be done the
setting button on the front panel (Please refer to section 4.2). The unit will
start up automatically after the setting procedure is finished and the new
settingswillbeexecuted. Thesenewsettingswillbekepteveniftheunitis
poweroff/onforanyreason.
STEP 1: The inverter should be turned off while resetting. Input batteries
STEP 2: Use an insulated stick to press the setting button and then turn on
STEP 3: Please refer to Table 4-1 and check whether the combination of
shouldbeconnectedandtheloadsshouldberemoved.
the power switch. Orange led indication will flash ON and OFF.
after pressing for 5 seconds, the inverter will send out a "Beep"
sound . Users can re l ease t he bu t ton a n d go i nto t h e set t ing
procedure.
output voltage and frequency is the one you need. If yes, please
jumptoSTEP 5.Ifnot,startfromSTEP 4.