Datasheet
SPECIFICATION
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT
VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
SAFETY STANDARDS
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
BATTERY LOW
ACCURRENT (Typ.)
1000ms,90ms/230VAC2000ms,90ms/115VACatfullload
24ms/230VAC20ms/115VACatfullload
88~264VAC124~370VDC
47~63Hz
80% 84% 84%
2.5A/115VAC1.5A/230VAC
COLDSTART 20A/115VAC40A/230VAC
<1mA /240VAC
CH1:105~135%CH2:0.51~0.9A ratedoutputpower
CH1:15.87~18.63V
10V 0.8V
19.5V(+1.5V,-1V) 39V 2V
CH1:31.74~37.26V CH1:62.1~72.9V
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
UL60950-1, TUVEN60950-1approved
CompliancetoEN55022(CISPR22) ,ClassB EN61000-3-2,-3
Complianceto EN55024,lightindustrylevel,criteria AEN61000-4-2,3,4,5,6,8,11,
-10~+60
(Referto"DeratingCurve")
20~90%RHnon-condensing
-20~+85 ,10~95%RH
0.03%/ (0~50 )
10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes
183.3Khrsmin.MIL-HDBK-217F(25 )
199*110*50mm(L*W*H)
0.88Kg;16pcs/15Kg/0.95CUFT
POWERFACTOR (Typ.) PF>0.92atfullload
155WSingleOutputwithBatteryCharger(UPSFunction)
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Battery low and battery polarity protection
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at PFC 67KHz, PWM 134KHz
2 years warranty
Features :
AD-155 se ri es
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
SAFETY &
EMC
(Note4)
PROTECTION
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC /25 /70%RH
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
CH1
OUTPUTNUMBER
AD-155A AD-155B AD-155C
13.8V 13.3V
CH2
27.1V
CH2
53.5V
CH2
27.6V
CH1
54V
CH1
10.5A 0.5A 0.5A 0.2A5A 2.7A
0~11.5A 0~0.5A 0~0.5A 0~0.5A0~5.5A 0~2.7A
151.55W 151.55W 156.5W
150mVp-p -------- -------- --------150mVp-p 240mVp-p
CH1:12~14.5V CH1:24~29V CH1:48~58V
2.0% -------- -------- --------
-------- -------- --------
-------- -------- --------
1.0% 1.0%
0.5% 0.5% 0.5%
0.5% 0.5% 0.5%
Protectiontype: ACChargingMode: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
UPSMode:Protectedbyinternalfuse
EMCIMMUNITY
EMCEMISSION
FileName:AD-155-SPEC2011-06-16