Datasheet

SPECIFICATION
MODEL
MTBF
DIMENSION
NOTE
PACKING
1. All parameters NOT specially mentioned are measured at 24VDC input, rated load and 25 of ambient temperature.
2. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer toEMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:DR-RDN20-SP EC 2014-04-16
20A Power Supply Redundancy Module
DR - RD N 2 0
Features :
OUTPUT
INPUT
OTHERS
ENVIRONMENT
DR-RDN20
REVERSE VOLTAGE (max.)
OUTPUT CURRENT (max.)
VOLTAGE DROP
LED INDICATORS
INPUT VOLTAGE RANGE
NUMBER OF INPUTS
INPUT CURRENT (max.)
INPUT VOLTAGE ALARM
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
VIBRATION
RELAY CONTACT RATING (max.)
30V
20A
0.6V
Two green LEDs indicating each input is "OK or fail"
21 ~ 28V
Two
20A per input
When input is > 20V( 5%) or < 30V( 5%) relay contacts± ±
30VDC, 1A
-40 ~ +70
20 ~ 90% RH non condensing
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mouning: Compliance to IEC60068-2-6
FUNCTION
996.8Khrs min. MIL-HDBK-217F (25 )
55.5*125.2*100mm (W*H*D)
0.5Kg; 20pcs/11Kg/1.29CUFT
Suitable for redundant operation of 24V system
Installed on DIN Rail TS35 / 7.5 or 15
Relay contact signal output and LED indicator for input failure alarm
Cooling by free air convection
3 years warranty
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
Terminal-Chassis :>100M Ohms / 500VDC / 25 / 70% RH
Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC
SAFETY &
EMC
(Note 2)
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A
PSU
PSU PSU
PSU PSU PSUPSU PSU PSU PSU
Load
Load
Load
Vout
DR-RDN20
DR-RDN20 DR-RDN20
DR-RDN20 DR-RDN20 DR-RDN20
Vout Vout Vout
Vout Vout
Vin A
Vin A Vin A
Vin A Vin AVin B
Vin B Vin B
Vin B
..............
Vin B
1. 1+1 Redundancy
Using 1 more PSU as the redundant unit
3. Single Use: Connecting only one PSU to one DR-RDN20 to reduce the stress of the diodes and hence increase the reliability
2. 1+N Redundancy: Using more PSUs as the redundant units to increase the reliability
Typical Application Notes
EMC IMMUNITY
EMC EMISSION
SAFETY STANDARDS UL508 approved

Summary of content (2 pages)