SPECIFICATION
MPS-65-3.3 MPS-65-5 MPS-65-7.5 MPS-65-12 MPS-65-13.5 MPS-65-15 MPS-65-24 MPS-65-27 MPS-65-48MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY(Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
Note.7
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
3.3V 5V 7.5V 12V 13.5V 15V 24V 27V 48V
12A 12A 8A 5.2A 4.7A 4.2A 2.7A 2.4A 1.35A
0 ~ 15.2A 0 ~ 13.8A 0 ~ 9.6A 0 ~ 6A 0 ~ 5.4A 0 ~ 4.8A 0 ~ 3A 0 ~ 2.7A 0 ~ 1.5A
39.6W 60W 60W 62.4W 63.45W 63W 64.8W 64.8W 64.8W
72W(+3.3V:50W;+5V:69W)with 18CFM min. Forced air convection
80mVp-p 100mVp-p 100mVp-p 100mVp-p 100mVp-p 100mVp-p 100mVp-p 100mVp-p 100mVp-p
±3.0% ±3.0% ±3.0% ±2.0%
±2.0%
±2.0% ±2.0%
±2.0%
±2.0%
±2.0%
±2.0%
±2.0%
±2.0%
±2.0%
±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
±3.0% ±3.0% ±3.0% ±2.0%
90 ~ 264VAC 127 ~ 370VDC
47 ~ 440Hz
66% 74% 76% 77% 78% 79% 80% 80% 80%
1.6A/115VAC 0.9A/230VAC
COLD START 17A/115VAC 35A/230VAC
73 ~ 105W (3.3V:51 ~ 75W)(5V:70 ~ 105W) rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Hiccup mode, recovers automatically after fault condition is removed
-20 ~ +85 , 10 ~ 95% RH
± 0.04%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
359.7Khrs min. MIL-HDBK-217F (25 )
127*76*42mm (L*W*H)
0.23Kg; 54pcs/14.6Kg/1.35CUFT
File Name :MPS-65-SPEC 20 14-01-2 9
800ms, 30ms/230VAC 800ms, 30ms/115VAC at full load
50ms/230VAC 16ms/115VAC at full load
-10 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
SAFETY STANDARDS
ANSI/AAMI ES60601-1, TUV EN60601-1, IEC60601-1 approved
Compliance to EN55011 (CISPR11) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN60601-1-2, medical level, criteria A
65W Single Output Medical Type
MPS -65
s eries
Universal AC input / Full range
Low leakage current <250 A
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Medical safety approved (2 x MOPP between primary to secondary)
100% full load burn-in test
Fixed switching frequency at 45KHz
3 years warranty
Features :
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG:100M Ohms / 500VDC / 25 / 70% RH
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer toEMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Mounting holes M1 and M2 should be grounded for EMI purposes.
6. Heat Sink HS1,HS2 can not be shorted.
7. .Touch current was measured from primary input to DC output
OUTPUT POWER (max.)
3.8 ~ 4.46V 5.75 ~ 6.75V 8.63 ~ 10.1V 13.8 ~ 16.2V 15.5 ~ 18.2V
17.25 ~ 20.25V
27.6 ~ 32.4V 31 ~ 36.45V 55.2 ~ 64.8V
VOLTAGE ADJ. RANGE
2.97 ~ 3.63V 4.5 ~ 5.5V 6.75 ~ 8.25V 10.8 ~ 13.2V 12.2 ~ 14.85V 13.5 ~ 16.5V 21.6 ~ 26.4V 24.3 ~ 29.7V 43.2 ~ 52.8V
EMC IMMUNITY
EMC EMISSION
Earth leakage current < 250 A/264VAC , Touch current < 60 A/264VAC
μ
μ