Datasheet

RCP s er i es
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Output of all the RCP-1000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
SPECIFICATION-RackSystem
RCP-3K1U -12
RCP-3K1U -24 RCP-3K1U -48
MODEL
VOLTAGERANGE Note.5
MODULE
OUTPUTVOLTAGE
RACK
MAX.OUTPUTCURRENT
MAX.OUTPUTPOWER Note.6
FREQUENCY RANGE
INPUT
OUTPUT
LEAKAGECURRENT
ACCURRENT (Typ.)FOREACHUNIT
90~264VAC 127~370VDC
2160W 3024W
180A 63A
12V
RCP-1UIorRCP-1UT
48V
RCP-1000-12 RCP-1000-24 RCP-1000-48
47~63Hz
<3.5mA /230VAC
8.5A/115VAC4.5A/230VAC 10.5A/115VAC5.5A/230VAC 11A/115VAC5.5A/230VAC
SAFETY STANDARDS
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
DIMENSION
PACKING
OTHERS
UL60950-1, TUVEN60950-1approved
CompliancetoEN55022(CISPR22)ClassB,EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN61000-6-2(EN50082-2),heavyindustrylevel,criteria A
-20~+60
(Referto"DeratingCurve")
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.02%/ (0~50 )
10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes
Rack483.6*350.8*44(L*W*H)
ENVIRONMENT
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.7KVDC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC /25 /70%RH
11Kg;1pcs/11Kg/2.67CUFT
FileName:RCP series-SPEC2011-12-19
ACFAIL SIGNAL
ACFAIL SIGNAL
DCOKSIGNAL
DCOKSIGNAL
REMOTESENSE
REMOTESENSE
REMOTEON/OFFCONTROL
REMOTEON/OFFCONTROL
AUXILIARY POWER
AUXILIARY POWER
The TTL signalout,refertofunctionmanual
The TTL signalout,refertofunctionmanual
Compensatevoltagedropontheloadwiringupto0.5V
The TTL signalout,refertofunctionmanual
The TTL signalout,refertofunctionmanual
Compensatevoltagedropontheloadwiringupto0.5V."LocalSense"shouldbeconnectedinordertogetthecorrectoutputvoltageifthe"RemoteSense"isnotused
ByelectricalsignalordrycontactON:shortOFF:open
ByelectricalsignalordrycontactON:shortOFF:open
5V@0.3A
5V@0.3A
FUNCTION
FUNCTION
Adjustmentofoutputvoltage,possiblebetween90~110%ofratedoutput
Adjustmentofoutputvoltage,possiblebetween90~110%ofratedoutput
Logic"High"forovertemperaturewarning,refertofunctionmanual
Logic"High"forovertemperaturewarning,refertofunctionmanual
SAFETY STANDARDS
WITHSTANDVOLTAGE
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
UL60950-1, TUVEN60950-1approved
-20~+60
(Referto"DeratingCurve")
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.02%/ (0~50 )
ENVIRONMENT
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.7KVDC
ISOLATIONRESISTANCE
MTBF
DIMENSION
PACKING
OTHERS
CompliancetoEN55022(CISPR22)ClassB,EN61000-3-2,-3
43.4Khrsmin.MIL-HDBK-217F(25 )
295*127*41mm(L*W*H)
SAFETY &
SAFETY &
EMC
(Note4)
EMC
(Note4)
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC /25 /70%RH
1.91Kg;6pcs/12.5Kg/1.04CUFT
OVERTEMP WARNING
OVERTEMP WARNING
OUTPUTVOLTAGETRIM
OUTPUTVOLTAGETRIM
RCP-1000-12 RCP-1000-24
MODEL
RCP-1000-48
10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN61000-6-2(EN50082-2),heavyindustrylevel,criteria A
1000~3000WFrontEndPowerSystem
2880W
120A
24V
EMCIMMUNITY
EMCIMMUNITY
EMCEMISSION
EMCEMISSION