Datasheet

SPECIFICATION
RSP-2400-12
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
CURRENT SHARING
OUTPUT VOLTAGE TRIM
Note.5
ALARM SIGNAL OUTPUT
REMOTE ON/OFF CONTROL
AUXILIARY POWER(AUX)
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
12V
166.7A
0 ~ 166.7A
2000.4W
150mVp-p
10.8 ~ 13.2V
±1.0%
±0.5%
±0.5%
1000ms, 80ms at full load
12ms at full load
180 ~ 264VAC 254 ~ 370VDC
47 ~ 63Hz
87%
15.5A/180VAC 12A/230VAC
60A/230VAC
<2.0mA / 240VAC
100 ~ 112% rated output power
13.8 ~ 16.8V
User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
28.8 ~ 33.6V
4.8 ~ 28V
57.6 ~ 67.2V
9.6 ~ 56V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70 (Refer to "Derating Curve")
Please see the Function Manual
Please see the Function Manual
2.4 ~ 13.2V
Please see the Function Manual
12V@0.1A(Only for Remote ON/OFF control)
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
± 0.05%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
106.7K hrs min. MIL-HDBK-217F (25 )
278*177.8*63.5mm (L*W*H)
3.3Kg; 4pcs/14.2Kg/1.89CUFT
90% 91%
±0.5% ±0.5%
±0.5% ±0.5%
±1.0% ±1.0%
150mVp-p
22 ~ 28V
200mVp-p
43 ~ 56V
24V
100A
0 ~ 100A
2400W
48V
50A
0 ~ 50A
2400W
RSP-2400-24 RSP-2400-48
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Can't use the PWM signal to control the output voltage.
6. PV(PIN3) and PS(PIN4) of CN1 or CN2 must be shorted if “Output Voltage TRIM” function is not used. Otherwise, the power supply unit will have no
output.
Fil e Name:RSP -2400-SPE C 201 4-08-0 5
POWER FACTOR (Typ.) 0.95/230VAC at full load
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
2400W Single Output Power Supply
RSP-2 400 series
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
AC input 180 ~ 264VAC
AC input active surge current limiting
High efficiency up to 91%
Built-in active PFC function,PF>0.95
Protections: Short circuit / Overload / Over voltage / Over temperature
/ Fan alarm
Forced air cooling by built-in DC with fan speed control function
Output voltage can be trimmed between 20~110% of the rated output voltage
High power density 12.5W/inch
3
Current sharing up to 3 units
Alarm signal output (relay contact and TTL signal)
Built-in 12V/0.1A auxiliary output for remote control
Built-in remote ON-OFF control
Built-in remote sense function
5 years warranty
Features :
EMC IMMUNITY
EMC EMISSION Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3