NOTE: EXIT ships standard RED. Refer to the Toggle Switch section for GREEN LED configuration.
BACK MOUNT
1. De-energize the circuit at an industry standard junction box, (not included), where the
exit sign is to be installed.
2. Remove EXIT stencil faceplate from housing. Remove RED lens from faceplate(see fig. A). Set aside.
3. Drill out the appropriate mounting paern and the wire pass hole in the EXIT back plate to fit
the junction box being used.
4. Feed the red, black and white wires through the center.
5. Remove the side mounting hole plug on the right side. Knockout lamp head mounting hole on
left side with flathead screwdriver.
6. Feed blue and yellow lamp head wire through side lamp head mounting hole(Step 1).
Aach first lamp head to housing by aligning tabs on lamp head assembly to lamp head mounting
slots on frame of housing (Step 2). Gently twirl lamp head clockwise to lock into place. An audible
click should be heard. Repeat to install remaining lamp head.
7. Feed lamp head wires in appropriate wire channels and connect lamp head leads to the exit sign lamp board.
8. Ensure fixture leads are fed through the back plate and connect to AC power leads coming into the junction box.
9. Connect RED leads to HOT of the power supply from 120-277V. Connecting the WHITE leads to the NEUTRAL of the supply.
10. HO only: make wiring connections to the appropriate remote lamp heads using the YELLOW(+) and the BLUE(-)
remote leads on the charger board. Cap off any UNUSED remote leads with wire nuts.
11. Fasten back plate to junction box cover.
12. Toggle the switchable to select GREEN, if applicable(see fig. C).
13. Connect the baery only after continuous AC power can be provided to the unit.
14. Remove knockout chevron(s) on the faceplate, as needed. Re-insert RED lens to faceplate (see fig. A)
(or GREEN if applicable, see fig. B). Secure EXIT stencil faceplate back onto housing.
1. De-energize the circuit at an industry standard junction box, (not included), where the exit sign is to be installed.
2. Remove EXIT stencil faceplate(see fig. A) from housing. Remove the RED lens from the faceplate. Set aside.
3. Remove the canopy kit, hardware pack and mounting plate from inside the EXIT and set aside.
4. Remove the mounting hole plug on the top or either side of the frame.