Datasheet

LTW 300 series
2 Wire Loop impedance testers
DESCRIPTION
The new Megger two wire earth loop testers verify the loop
impedance of a live electrical circuit, ie without the need to
disconnect the electrical supply. The new LTW300 series
instruments offer a 2 wire loop testing solution that does
not trip 30 mA RCDs and can be used on a wide range of
voltages.
The new LTW300’s offer a range of features to make earth
loop testing safer and easier.
The range consists of:
n LTW315 - 2 Wire loop impedance measurement
n LTW325 - 2 wire + maxZ + (R1+R2)
n LTW335 - 2 wire + maxZ + (R1+R2) + Download
n LTW425 - 2 wire + maxZ + (R1+R2) + 0.001 Ω
2 Wire testing
A loop test is performed with only 2 test leads. This can be
either:
n Phase to Earth
n Phase to Neutral
n Phase to Phase
Testing is simple, as there is no need for a 3rd wire to be
connected, which can cause confusion when trying to
identify which part of the circuit is being tested.
Test results are displayed to a resolution of 0.01 Ω.
Non-trip loop testing
The LTW300 series are guaranteed not to trip working RCDs
of 30 mA, using the No-trip loop test.
3 Phase circuits with RCD protection can also be tested, as
all test modes operate on single and three phase systems.
The loop test runs for approximately 10 seconds, with an
additional 10 seconds if the instrument detects electrical
noise on the supply that could otherwise cause errors on
the test result.
High current loop testing
For supplies that do not have an RCD fitted the high current test
should be used, as there is no risk of tripping and RCD.
Noise detection (only applies to No-trip tests)
The LTW uses sophisticated noise detection circuitry which
continually monitors the supply whilst performing a loop
test to ensure the accuracy of the result has not been
compromised by the effects of electrical noise from plant
and services.
Two operational modes are available:
a) 10 second test:
Always performs a 10s test and if noise is detected displays a
warning at the end of the test
n 2 Wire Non-tripping loop tester
n 50 V to 440 V operation
n 110 V centre-tap loop testing
n CATIV installation testing
n AUTO start - operation
n 0.001 Ω resolution (LTW425)
LTW300
2 Wire loop impedance testers