Supplement to Operating Instructions UFP 600 TS/800 TS
4.  Temperature control programme suggestion on 
MemoryCard
Ramp. 
no.
Time
tem-
pera-
ture
Fan Flap Ramp close 
statement
Description
1 0:01 160 °C 100 % CLOSE SPWT(T) Quickly heating up to set 
temperature. Wait until the 
setpoint temperature has 
been reached.
2 2:00 160 °C 100 % CLOSE NEXT Hold time 
3 0:01 45 °C 100 % OPEN SPWT(T) Cooling down to unloading 
temperature. If necessary, 
open the air flap for faster 
cooling down.
4 0:01 20 °C OFF CLOSE END Turning off the fan and close 
programme
The confirmation button cannot be pressed until all doors have been closed. This way, it 
is not possible to open both doors at the same time.
5. Attachment
 ► Memory medium with PLC programme: 2011-07-08 ra UFP600TS
 ► Function block diagram (FBD) of the PLC
 ► Parameters/block diagram of the PLC