Operating instructions

A-2 ELEVATED RISE THROUGH-THE-WALL VENTING FOR NG AND LPG
The minimum vertical rise from top of fireplace, is 48 in. when used with the maximum horizontal run of 16 ft.
For other venting configurations within these maximum limits see pg. 10.
NOTE: All horizontal runs of vent pipes must have a ¼" rise for every 1' of run toward the termination. Never
allow the vent to run downward. This will cause high temperatures and the possibility of a fire.
USING OFFSETS AND RETURNS: A single 90
º vertical-to-horizontal elbow is already calculated into the
allowable maximum 16' horizontal run. Each additional 90
º elbow reduces the maximum horizontal distance
by 3'. A maximum of two 90° or four 45° elbows, in addition to the first 90
o
elbow, can be used (total equiva-
lent of three (3) 90
o
elbows in entire vent system. 45º elbows reduce the maximum horizontal distance by 1½ '.
SUPPORT: Horizontal runs of pipe will require one vent support for every 3 ft. of pipe.
CAUTION: Be sure to maintain 1" air space clearances to any combustibles around all pipe sections that are
vertical. Be sure to maintain 1” air space clearances to any combustibles on the sides and below all horizontal
pipe sections and elbows and 2" from the top of all horizontal pipes and fittings.
1. Position fireplace in desired location. See pg. 8 for guidelines on proper vent cap placement on exterior of
home. Check to determine if wall studs are in the way when vent system is attached. If this is the case you
may need to adjust the fireplace location.
2. Locate position where vent pipe will pass through any ceilings and will penetrate the outside wall. Since
vent pipe sections "overlap" we suggest pre-assembling and measuring the total vent pipe run so you can
more accurately locate the point where the vent pipe will penetrate the outside wall. (See FIGURE 3: Exte-
rior Vent Locations, pg.8). Be sure all vent components are properly twist locked and leak-proof. Be sure
1000
º silicate sealant (Millpak #65-06-00909) is used in the inner joints of all pipe sections (Dura Vent
only).
IMPORTANT: REFER TO DRAWINGS ON PAGE 10 & 11 WHILE FOLLOWING THESE
INSTRUCTIONS.
*NOTE: DO NOT SEPARATE TELESCOPING SECTIONS USE AS COMPLETE ASSEMBLIES.
3. Cut and frame a 10-3/4" x 10-3/4" opening in the outside wall and in any ceiling openings. The outside wall
hole must be positioned so the vent system will have a ¼ " rise per foot of run AND be perpendicular to the
wall. The height of the opening must be located to meet all local and national building codes and not allow
the termination to be easily blocked or obstructed. A ceiling fire stop spacer is required at any floor (ceil-
ing) opening.
4. Connect a 90° elbow to the fireplace adapter on top of fireplace vent outlet.
5. Always use a Wall Thimble (#45-01-00229) when penetrating a combustible wall.
6. The horizontal pipe must end flush with the exterior wall of the home. Horizontal pipe will require a proper
support (part #45-01-00234) every 3 ft. of vent pipe. THERE MUST BE A MINIMUM OF 1"
CLEARANCE TO COMBUSTIBLES FROM ALL VENT PIECES (2" above horizontal runs). From the
exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly secure the
vent cap to the wall with screws. Seal with high quality caulking.
NOTE: Venting terminal should not be recessed into the wall or siding.
13