WARNING
DO NOT PROCEED WITH OPERATION OF THIS FIREPLACE
UNLESS BURNER "CYCLES" ON/OFF WITHOUT DELAYS!
CHECKING FOR NORMAL BURNER (S) IGNITION CHARACTERISTICS
Once the conversion to LPG and all the above steps have been completed, install Burner Media and light the main burner.
On the Remote Transmitter, push On/Off button to ON . Change Thermostat Mode to "MANUAL". The pilot system will
begin to spark and then the Main burner should light and flame should not "lift" off burner. If there is any delay in ignition
or if flame is "lifting off" burner, turn off burner and carefully check for proper installation of burner media, vent system and
proper pilot flame impingement on burner. Burner Media must not block pilot flame. Vent system must be leak proof.
ATTACHING LPG CONVERSION LABELS AND HIGH ALTITUDE DERATION LABEL
Two printed informational labels are included with the LPG Conversion Kit. Attach these two labels to the back surface of
the Serial Number Plate that is located in the convection air cavity below the firebox. If you are derating this appliance at a
high altitude, also attach the High Altitude Deration Label, supplied in the Owner’s Manual Packet, to this same surface.
Prior to attaching the labels, fill in all the information that is requested in these labels.
For installations from 610-1370 meters (2000-4500 ft.) the orifice size (DMS) for natural and propane gas are _31_ and
_49_, respectively. See data plate for additional information. For high altitude installations consult the local gas distribu-
tor or the authority having jurisdiction for proper rating methods. If the installer must convert the unit to adjust for varying
altitudes, the information sticker must be filled out by the installer and adhered to the appliance at the time of conversion.
«Cet appareil est equipé pour des altitudes compries entre 0 et 2000 pieds (0-610 m) seulement»
This appliance has been converted for use at an altitude of ______________
Orifice size _______________ Manifold Pressure ________________
Input (Btu/h)_______________ Fuel Type _______________________
Date of conversion _________ Converted by _____________________
«Cet appreeil a été converti au ____
Injecteur ________
Pression à la tubulure d'alimentation _____________
Déoit calorifique ______________