EJA / EJX Accuracy Utility 
This program is designed to aid in the calibration of the Yokogawa EJA / EJX Pressure Transmitter series. 
The program will calculate the maximum error based on design accuracy of the EJA / EJX and the pressure 
module used when performing a calibration with the MFT. 
Get HART Data 
If the EJA / EJX has HART Communications, the program will automatically read all necessary 
information needed to perform the calculations. If the EJA / EJX does not have HART Communications 
an “EJA not found” error will be displayed. Data can be input manually into the program for non-HART 
units. 
EJA Model: 
This data can be obtained automatically by selecting “Get HART Data” or manually input by selecting 
the Chng soft key. 
Pres Unit: 
The pressure units can be obtained automatically by selecting “Get HART Data” or manually input by 
selecting the Chng soft key. 
Zero (LRV): 
The Low Range Value can be obtained automatically by selecting “Get HART Data” or manually input 
by selecting the Chng soft key. 
Span (HRV): 
The High Range Value can be obtained automatically by selecting “Get HART Data” or manually input 
by selecting the Chng soft key. 
Module: 
Select the position of the pressure module (S1, S2, S3, or None) used for the calibration. If a module is 
selected then the accuracy of the pressure module is used to determine overall error. If “None” is 
selected then the design accuracy of the EJA / EJX is calculated. If no pressure module is installed, 
“n/a” is displayed and the design accuracy of the EJA / EJX is calculated. 
Calculate 
Calculates data and goes to the results screen. If a pressure module was selected, the message 
“Accuracy is dependent on the span of the pressure module used” is displayed for 3 seconds. 
Accuracy % 
This is the maximum error of the calibration of the EJA / EJX in % of span. If a pressure module was 
selected, then the accuracy of the pressure module is included in the calculation to determine overall 
error. If “None” is selected then the design accuracy of the EJA / EJX is used to calculate the overall 
error. 
Accuracy mA 
This is the maximum error of the calibration of the unit in mA. If a pressure module was selected then 
the accuracy of the pressure module is included in the calculation to determine overall error. If “None” is 
selected then the design accuracy of the EJA / EJX is used to calculate the overall error. 
Min Span 
Displays the minimum span of the EJA / EJX unit. 
Max Span 
Displays the maximum span of the EJA / EJX unit. 
LRL 
Displays the lower Range Limit of the EJA / EJX unit. 
URL 
Displays the upper Range Limit of the EJA / EJX unit. 