Manual
25
Select the Function menu option under the Meas/Sim line to select the needed MFT operation for the 
device under test’s input. The following screen is shown: 
P Meas: is selected for P transmitter, P/I converter, P/P converter, or P switch calibrations. 
T/C Meas:  is selected for t/c comparison testing or bulb type T switch calibrations 
RTD Meas:  is selected for RTD comparison testing or bulb type T switch calibrations. 
VMA Meas: is generally not used 
T/C Sim:  is selected for T/C temperature transmitter calibration 
RTD Sim:  is selected for RTD T transmitter calibrations or RTD switches. 
VMA Sim:  is selected for I/P converter calibrations and some special applications 
Press the Back soft key if you choose not to make any changes. The MFT will then return to 
the Calibrate key main menu screen. 
Select the Location menu option under the Meas/Sim line to select the sensor needed for the 
Meas/Sim type displayed (previously selected). The following screen is shown. 
Select the Function menu option under the Measure line to select the needed MFT operation for the 
device under test’s output. The following screen is shown: 
Cal 
Meas/Sim: P Meas 
  S1: RIO 
  S2: DDN 
 S3: TIO 
Up Down Select Back 
Cal 
Meas/Sim: P Meas 
 P Meas 
 TC Meas 
 RTD Meas 
 VMA Meas 
 TC Sim 
 RTD Sim 
 VMA Sim 
Up Down Select Back 
Cal 
Meas: IV Meas 
 P Meas 
 TC Meas 
 RTD Meas 
 VMA Meas 
 IV Meas 
Up Down Select Back 