Installation manual
23
BY PASS
CONDENSA 5.24 - 3.15
SBLOCCO
2.11 Filling the condensate drainage system.
Take off the plug on the condensate drainage system and fill it with water amounting to 1
glass so that flue gases do not come out.
Attention. Do not operate the boiler if the condense drainage system is empty. It
may cause intoxication from burnt gas.
2.12 System start-up.
Before starting up the boiler, check that the relevant actual rules have been performed.
Make sure that:
all fuel pipe connections are tight and completely sealed; first check the with the
isolation valve closed, then with the isolation valve open (while keeping the gas valve
closed). No gas presence is supposed to be indicated by the gas meter in 10 minutes;
the boiler is supplied with preset gas;
the gas flow rate is as specified in this manual (see par. 3.7);
the main switch is working correctly;
the air/flue ducts (if present) are not obstructed. Do not start up the boiler if the controls
do not satisfy the requirements.
2.13 The pump.
Our boilers are provided with pump.
After long periods of disuse residue can cause the block pump. To reset proceed as
follows: unscrew the knob, rotate with a screwdriver until open and then tighten. Be
careful not to damage the pump.
Never operate the pump without water
Graphic of the available head (dotted area) and the curves of the pump flow/head
characteristics (dotted)