Installation manual

29
2.23 Separate air inlet/flue outlet system.
Type C43
Please see also the specific catalogue "Air/flue Kits" - KIT AC for further information.
Ø80
Ø80
Sigillare con malta
di cemento
Sigillare con silicone
o malta di cemento
Inclinare verso
l'alto di 5 mm/m.
Inclinare verso il
basso di 5 mm/m.
Guaina in PVC
Guaina metallica
120
1 2 4
6
Espulsione fumi
Aspirazione aria
1) Flue outlet terminal with grill.
2) Ø80 M.F. pipe (it can be shortened if necessary or extended up to 20 m with 1 m or 0,5 m).
3) Multi-directional 90° bends Ø80 M.F.
4Air inlet terminal with grill.
6) Taps for flue/air analysis.
Specific outlet needs may be resolved by placing two separate pipes ø 80 mm, one for air
inlet and one for flue outlet up to a total length of the two pipes of m. 40.
This allows an increased installation flexibility, beside a differential orientation in any
direction. When having to cross rooms which are usually heated, the air duct may cause
condense accumulation, therefore a suitable insulation can be applied on demand.
When having to cross
walls or barriers which
could deteriorate due to
the heat, the flue terminal
must be installed with a
suitable isolating sleeve.
The air inlet and flue outlet
ducts will be installed with
a slight downward slant to
avoid rainwater from
entering the boiler.
Perform assembly
according to the
indications in the diagram
and make sure that each
catch is equipped with a
gasket. The length of the
air inlet and of the flue
ducts can be different.
They can be shortened or
lengthened by means of
0.5 m.
Seal with silicon
or mortar of
cement
Plastic sheath
Metallic sheath
Seal with mortar of
cement
Slope 5
mm
downwar
Air inlet
Slope 5
mm
downwar
Flue outlet
Attention. The outlet flange adaptor shown must no
t be used.
Particolare tubi
sdoppiati
Fig 12
Separate pipes
Flue outlet pipe
(to be conneted to the
boiler)
Air inlet pipe with adaptor