Designed for installation in all modular electrical
enclosures and switchboards.
Mounting on symmetrical rail with bistable lock.
Easy connection thanks to serrated tunnel terminals
with guard.
Captive screws with mixed +/- recess.
CONNECTION DIA
CONNECTION DIA
GRAM
GRAM
TECHNICAL D
TECHNICAL D
A
A
T
T
A
A
Electrical data:
Voltage: 230 V AC +/-10%.
Frequency: 50..60 Hz.
Consumption: max. 6 VA.
Saving of program and time by lithium battery:
lifetime: 12 years except for cat. no. 15720: 5 years,
back-up time: 5 cumulated years of mains power cut
except for cat. no. 15720: 3 years.
Accuracy: +/- 1 s a day at 20°C: time base
synchronised on the mains.
Contact rating:
16 A/ 250 V AC (cos ϕ = 1),
10 A/ 250 V AC (cos ϕ = 0.6).
Mechanical data:
Connection:
tunnel terminals for cables up to 6 mm2,
recommended screwdriver: posidriv 1 or flat 0.8x4 mm.
Dimensions:
5 modules: H = 82; W = 90; D = 60 mm.
Weight (g): 190.
ENVIR
ENVIR
ONMENT
ONMENT
Complies with standard EN 60730.
Safety class: 2.
Degree of protection:
front face: IP 40,
terminals: IP 20.
Ambient installation temperature:
-10°C to +50°C.
Storage temperature:
-25°C to +70°C.
DESCRIPTION
DESCRIPTION
Date
Time: display of operation on mains ":" or battery " : "
Day (1: Monday, 2: Tuesday, etc.)
Display of output contact status (Channel 1/
Channel 2 in turn for cat. no. 15722 and 15723)
Display of " On " periods by 30-minute segment
(e.g. displayed: 6.30 am to 3 pm and 9 pm to
midnight for channel 2)
Operating mode:
Auto: automatic operation according to the
memorised program,
Prog.: programming, verification,
modification and deletion
: modification of time and choice of
automatic " summer time / winter time "
switching date,
Man: programming the " random " and
" holiday " functions
: programming pulses
Indication of " ON override " and of
"random " and " holiday " operation.
Selection of operating modes
Value setting and navigation key
Flashing information validation key
Reinitialisation key: deletion of program, date, time and
choice of language.
SCHNEIDER ELECTRIC HELP CENTRE
Tel: 1300 369 233
Fax: 1300 369 288
Email: help@schneider.com.au
www.schneider-electric.com.au
AUS01PL31-A
description number memory back-lighting catalogue
of (number absence number
channels of spaces) for holidays
random
pulse
HP 24 h and/or 7 d
IHP 1c 1 28 15720
IHP + 1c 1 42 x 15721
IHP 2c 2 42 15722
IHP + 2c 2 42 x 15723
15720
CHOICE
CHOICE
T
T
ABLE
ABLE
4
5
7
6
2
3
1
Menu
Res
2
1
ok
12
345 67
3
0
6
22:30
C2 O
15 99
Auto
Prog
n
03
Man
9
12
15 18 21 24
8
11
9
10
M
N
L
N246
230-240V
50-60Hz
-10 T 50
L
135
16(10)A 250V
16(10)A 250V
C2
C1
Menu
Res
2
1
ok
M
N
L
N246
230-240V
50-60Hz
-10 T 50
12
345 67
3
0
6
22:30
C2 O
15 99
Auto
Prog
L
135
16(10)A 250V
16(10)A 250V
ff
03
Man
C2
C1
9
12
15 18 21 24
L
N
1
2
3
4
5
6
7
8
9
10
11
.