COMPACT¨ NSF and NSJ 150 to 600 A circuit breakers Class 615 CONTENTS Description Page General characteristics .............................................................................................. 3 Circuit breakers .......................................................................................................... 6 Switches ................................................................................................................... 14 Motor circuit protectors ........................
COMPACT® NSF and NSJ 150 to 600 A circuit breakers page ® ® COMPACT NS circuit breaker The COMPACT circuit breaker line 2 General characteristics 3 Circuit breakers 6 Trip units 8 Switches 14 Motor circuit protectors 16 Installation and connections 18 Connections 20 Accessories 22 Fixed-mounted 32 Plug-in and drawout mounting 34 Motor operators 36 Rotary operating handles 38 Front accessories 40 Interlocking systems 41 Connections 42 Auxiliary circuits 44 Trip curves 46
COMPACT® NS circuit breaker: functions and characteristics The COMPACT® circuit breaker line E28473 Circuit breakers page 6 push to trip Rated current (A) COMPACT® 15–100 15–250 150–600 400–1200 1250–2500 NSE100 Interrupting N rating H at 480 V L 18 – – NSF150 NSF250 35 65 – NSJ400 NSJ600 35 65 100 CK400– CK1200 50 65 150 CM1250– CM2500 – 85 – Rated current (A) COMPACT® 70 150, 250 400, 600 800, 1200 1600–2500 NSE100A NSF150A NSF250A NSJ400A NSJ600A CK800NA CM1600HA CM2000HA CM250
COMPACT® NS circuit breaker: functions and characteristics General characteristics E28472 Compliance with standards MERLIN GERIN compact NSF 250 N 600Y/347V 50/60Hz UL/CSA interrupting ratings RMS sym. Amps 240V ac 480V ac 600Y/347V ac 65k 35k 18k current limiting (see curves in catalog) IEC947.
® COMPACT NS circuit breaker: functions and characteristics General characteristics 044334 Suitability for isolation (positive contact indication) All COMPACT® NS circuit breakers and switches are suitable for isolation as defined in the IEC 947-2 Standard: ■ The isolation position corresponds to the O (OFF position); ■ The operating handle cannot indicate the OFF position unless the contacts E18569 E36863 are open; ■ Padlocks may not be installed unless the contacts are open.
® COMPACT NS circuit breaker: functions and characteristics E28801 General characteristics The limiting capacity of a circuit breaker is its ability to limit short-circuit currents. Circuit breaker current limiting capacity Exceptional current limiting capacity The exceptional limiting capacity of the COMPACT® NS line is due to the double break technique (very rapid natural repulsion of contacts and the appearance of two arc voltages in series with a very steep wavefront).
® COMPACT NS circuit breaker: functions and characteristics Circuit breakers E28017 Ratings and interrupting ratings UL 489 Listed ratings COMPACT circuit breakers ® push to trip Number of poles Rated voltage (V) Rated current (A) In AC 50/60 Hz 40°C Interrupting ratings (kA rms) 240 V 480 V 600Y/347 V 600 V IEC 947-2 and EN 60947-2 ratings ® COMPACT circuit breakers 045345 Number of poles Rated insulation voltage (V) Ui Rated impulse Uimp withstand voltage (kV) Rated operational voltage (V) Ue
® COMPACT NS circuit breaker: functions and characteristics Circuit breakers NSF150 NSF250 NSJ400 NSJ600 3 600Y/347 150 N 65 35 18 3 600Y/347 250 N 65 35 18 3 600 400 (100% rated circuit breaker) N H L 65 100 150 35 65 100 3 600 600 N 65 35 H 100 65 L 150 100 18 18 25 25 H 100 70 65 50 35 20 85 85 100% A L 150 150 130 70 50 35 H 100 65 25 H 100 65 25 25 25 NSF150 NSF250 NSJ400 NSJ600 3 750 8 3 750 8 3 750 8 3 750 8 690 500 150 N 85 36 35 30 22 8 50 50 100% A 690 500 250 N 85 3
® COMPACT NS circuit breaker: functions and characteristics Trip units Trip units for COMPACT® NSF150 and NSF250 circuit breakers COMPACT® NSF150 and NSF250 circuit breakers are equipped with thermal-magnetic (TM) trip units. t 1 1 2 E28020 Ir Im 10 TM 250 D 250A / 40°C 5 9 250 A 8 2 6 7 Ir x 250 A Im 0 Ir Im I Protection ■ Against overload (1) with a fixed thermal protection. ■ Against short circuits (2) with fixed (on NSF150) or adjustable (on NSF250) magnetic protection.
® COMPACT NS circuit breaker: functions and characteristics Trip units Trip units for COMPACT® NSJ400 and NSJ600 circuit breakers COMPACT® NSJ400 and NSJ600 circuit breakers are equipped with current sensors and electronic trip units. Current sensors Four different sizes are available and can be mounted with all trip units: ■ NSJ400: 150, 250 and 400 A; ■ NSJ600: 600 A; Trip units STR23SP and STR53UP Protection for loads, from 60 to 600 A.
® COMPACT NS circuit breaker: functions and characteristics Trip units Trip units for COMPACT® NSJ400 and NSJ600 circuit breakers 1 STR 23 SP Io = sensor .8 .9 .7 .63 1 .5 x In + 4 3 2 Ir long time .88 .85 .8 .9 .93 .95 .
® COMPACT NS circuit breaker: functions and characteristics Trip units Trip units for COMPACT® NSJ400 and NSJ600 circuit breakers 8 1 3 2 6 4 5 %Ir >Ir 9 E21004 E36298 Electronic trip unit STR53UP 7 t 1 6 2 STR 53 UP Io .7 Isd Ir .8 .9 1 .6 .90 .93 .88 .95 .98 .85 1 .5 .8 x In x Io tr test + 1 - 4 8 6 7 2 1.5 7 x Ir .3 .3 .2 .1 .1 0,5 8 (s) @ 6 Ir 0 0 on I2t off test 3 .5 .6 1.5 .4 8 9 2 7 fault µP 4 6 4 5 3 >Ig Ig Ii tsd (s).2 2 >Isd .7 9 .
® COMPACT NS circuit breaker: functions and characteristics Trip units Options for electronic trip unit STR53UP "Ground-fault" protection (T) (see (6) and (7), page 11) Type Tripping threshold Ih accuracy maximum overcurrent time before tripping Tripping time (ms) total breaking time residual current adjustable (8 settings) 0.
® COMPACT NS circuit breaker: functions and characteristics Trip units Electronic trip unit test kits 047035 The two test kits presented below are compatible with COMPACT® and ® MASTERPACT circuit breakers. Tests performed by test kits are only functional tests designed to electrically test the operating integrity of the trip unit, the flux shifter and the mechanical operation of the circuit breaker. Tests are not designed to calibrate the circuit breaker.
® COMPACT NS circuit breaker: functions and characteristics E28017 Switches Ratings and interrupting ratings UL 1087 Listed ratings COMPACT switches ® push to trip Number of poles Rated voltage (V) Rated current (A) AC 50/60 Hz IEC 947-3 ratings ® COMPACT switches Number of poles Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue Rated operational current (V) Ie Making capacity (kA peak) Short-time withstand current (kA rms) Icw AC 50/60 Hz
® COMPACT NS circuit breaker: functions and characteristics Switches NSF150A NSF250A NSJ400A NSJ600A 3 600Y/347 150 3 600Y/347 250 3 600 400 3 600 600 NSF150A NSF250A NSJ400A NSJ600A 3 750 8 690 500 160 160 160 3.6 2.5 3 3 750 8 690 500 250 250 250 4.9 3.5 3 3 750 8 690 500 400 400 400 7.1 5 3 3 750 8 690 500 630 630 630 8.
® COMPACT NS circuit breaker: functions and characteristics Motor circuit protectors E36161 Ratings UL 489 Recognized Component COMPACT circuit breakers ® push to trip Number of poles Rated voltage (V) Rated current (A) Magnetic trip setting In Im AC 50/60 Hz 40°C IEC 947-2 and EN 60947-2 ratings ® COMPACT circuit breakers Number of poles Rated insulation voltage (V) Ui Rated impulse withstand Uimp voltage (kV) Rated operational voltage (V) Ue Rated current (A) In AC 50/60 Hz DC 40°C Ultimate br
® COMPACT NS circuit breaker: functions and characteristics Motor circuit protectors NSF150HC NSF250HC NSJ400HC NSJ600HC 3 600Y/347 150 900-1800 3 600Y/347 200 1000-2000 3 600 400 (100% rated circuit breaker) 2000-4000 3 600 600 3000-6000 250 1250-2500 NSF150HC NSF250HC NSJ400HC NSJ600HC 3 750 8 3 750 8 3 750 8 3 750 8 690 500 150 HC 100 70 65 50 35 10 85 85 100% A 690 500 200 HC 100 70 65 50 35 10 85 85 100% A 690 500 400 HC 100 70 65 30 35 20 85 85 100% A 690 500 600 HC 100 70 65 30
® COMPACT NS circuit breaker: functions and characteristics Installation and connections Fixed mounting Mounting on backplate E28023 E28024 Mounting on rails Flush mounting E36968 Refer to circuit breaker installation instructions before installing circuit breaker, accessories or wiring. push to trip push to trip push to trip Connections See pages 20 and 21 for details. COMPACT® NSF and NSJ circuit breakers are suitable for reverse feeding.
® COMPACT NS circuit breaker: functions and characteristics Installation and connections E21282 86025 Drawout mounting Connected Disconnected Removed The chassis is made up of two side plates installed on the base and two other plates mounted on the circuit breaker.
® COMPACT NS circuit breaker: functions and characteristics Connections Front connection E28028 E29280 E29229 Connection to cables ® ■ Cable connectors for COMPACT NSF150 and NSF250 circuit breakers lay on top of the circuit breaker terminals. They are held in place by a plastic lug pack which is screwed into the circuit breaker case.
® COMPACT NS circuit breaker: functions and characteristics Connections Rear connection Fixed mounting E28033 E29145 For connection of bars or cables with compression lugs. Rear connections are easily installed on the circuit breaker terminals. The same connection may be installed flat, edgewise or at a 45° angle. All combinations are possible. The circuit breaker is mounted on a backplate.
® COMPACT NS circuit breaker: functions and characteristics Accessories Location Internal accessories comply with requirements of Underwriters Laboratories Inc. UL 489 and Canadian Standard Association C22.2 No.5.1 Standards. All internal accessories are Listed for fixed installation per UL file E103955 and Certified under CSA file LR 69561.
® COMPACT NS circuit breaker: functions and characteristics Accessories Automatic secondary disconnecting blocks Accessory circuits exit the circuit breaker via one to three secondary disconnecting blocks (nine wires each). For COMPACT® NSJ400/600 circuit breakers connection wires for the options installed with trip unit STR53UP also exit via the automatic secondary disconnecting blocks.
® COMPACT NS circuit breaker: functions and characteristics Accessories Auxiliary and alarm switches Changeover switches 044314 Auxiliary switches provide remote information of the circuit breaker status and can thus be used for indications, electrical locking, relays, etc.
® COMPACT NS circuit breaker: functions and characteristics Accessories Shunt trip and undervoltage trip 044313 A voltage release can be used to trip the circuit breaker via a control signal.
® COMPACT NS circuit breaker: functions and characteristics Accessories Motor operator 86012 The motor operator remotely operates the circuit breaker featuring easy and sure operation: ■ All circuit breaker indications and information remain visible and accessible, including trip units settings and circuit breaker connection; ■ Suitability for isolation is maintained and padlocking remains possible; ■ Double insulation front face.
® COMPACT NS circuit breaker: functions and characteristics Accessories Rotary operating handles Operation The direct rotary handle maintains: Suitability for isolation; Indication of three positions O (off), I (on) and tripped; Access to the "push-to-trip" button; Visibility of and access to trip unit settings; I/ON (Closed) E36970 86037 ■ ❑ ❑ ❑ ❑ Closing Tripped Reset I tripped reset O/OFF (Open isolated) COMPACT® NS250N circuit breaker with direct rotary handle.
® COMPACT NS circuit breaker: functions and characteristics Accessories Cable operating handle Flange-mounted handle cable operating mechanism E34103 Operation ■ ❑ ❑ ❑ ❑ ❑ push to trip The cable operator maintains: Suitability for isolation, Indication of three positions O (Off), I (On) and tripped, Access to push-to-test, The circuit breaker may be locked in the off position by one to three padlocks, Door can be locked closed due to interlocking features of the handle operator.
® COMPACT NS circuit breaker: functions and characteristics Accessories Interlocking systems Interlocking prevents the simultaneous closing of two circuit breakers.
® COMPACT NS circuit breaker: functions and characteristics Accessories Front panel escutcheons For fixed or plug-in mounting Door escutcheon provides better appearance of the door contact. E28043 Front panel escutcheons for toggle Secures to the panel, from the front. push to trip E21265 E23938 Front panel escutcheon for motor operator module or rotary operating handle Secures to the panel by four screws, from the front. 22 O OFFOFF O ON I d arge d disch arge disch 8 ∅ 5......
® COMPACT NS circuit breaker: functions and characteristics Accessories E28045 Outgoing circuit identification UMP M A IN P N MAI P push to trip COMPACT® NS circuit breakers come with labels designed for handwritten indications. It is also possible to use preprinted Telemecanique labels, catalog No. AB1: ■ COMPACT® NSF150–NSF250 circuit breakers: eight characters; ■ COMPACT® NSJ400–NSJ600 circuit breakers: sixteen characters.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Fixed-mounted inch mm E29151 E29150 Dimensions H3 E36973 H1 Electrical clearances H54 13.8 35 X X H H2 H53 (a) Y P1 P2 P4 0.4 10 L L1 0.4 10 (a) short terminal covers for rear connection Z 13.8 35 Mounting Mounting on backplate Mounting on rails K1 E21511 E21507 K1 K1 K U (e) G1 X G G5 G1 G4 ∅T K1 K X G ∅T Y ∅T4 (d) Y (d) only for rear connected circuit breakers. (e) U ≤ 0.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Fixed-mounted inch mm Front panel cutouts E29234 E21609 With escutcheon E21602 With toggle boot C7 X C21 X X C20 C6 Y R6 R7 Y R12 R13 P6 Z Front accessories: see page 30 NSF150/250N/H/L NSJ400/600N/H/L NSF150/250N/H/L NSJ400/600N/H/L NSF150/250N/H/L NSJ400/600N/H/L NSF150/250N/H/L NSJ400/600N/H/L (inch) (mm) (inch) (mm) C 1.14 29 1.63 41.5 C1 2.99 76 4.56 116 C2 2.12 54 3.64 92.5 C3 4.25 108 7.24 184 C6 1.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Plug-in and drawout mounting inch mm Dimensions E28049 Plug-in (on base) M ( ) Z * E21522 K1 H17 G11 X X H16 G10 Y P7 P8 P9 L L1 P4 Drawout (on chassis) E21584 E28250 M H19 X X H18 ( ) * Y Z P7 P8 P9 P2 P4 L6 L7 L8 P12 (*) Short terminal covers.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Plug-in and drawout mounting Mounting inch mm E21533 On rails (plug-in base or chassis) K21 K20 U X G21 G20 Y ∅T Front panel cutouts Plug-in mounting See fixed-mounted installation page 32.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Dimensions inch mm E29154 E29155 Motor operators H20 H21 H22 X X H23 Y L P33 P32 L12 L11 L1 Z E21614 E29157 Front panel cutouts X C23 X C22 Y R14 R15 P45 Z Dimension table NSF150/250N/H/L NSJ400/600N/H/L NSF150/250N/H/L NSJ400/600N/H/L (inch) (mm) (inch) (mm) C22 1.14 29 1.63 41.5 (inch) (mm) (inch) (mm) R15 3.81 97 5.07 129 C23 2.99 76 4.96 126 H20 2.46 62.5 3.93 100 H21 3.81 97 5.98 152 H22 1.79 45.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Cable operating handles inch mm E44366 E44367 Compact NSF 5.19 132 4.86 123 11.32 287 4.31 109 0.31 8 1.06 27 7.01 178 10.38 264 9.38 238 8.75 222 E43608 E43607 Compact NSJ 7.996 203 4.31 184 11.32 287 4.31 109 7.01 178 0.31 8 1.06 27 10.38 264 9.38 238 13.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Rotary operating handles inch mm Dimensions E29159 E29158 L12 60° H23 X I H24 DD 60° H20 X O Y L15 P34 P35 (a) L L11 L1 P36 (b) P37 (c) Z (a) Without keylock (b) With RonisTM keylock (c) With ProfaluxTM keylock Ronis and Profalux are trademarks of HF Sécurité Front panel cutouts X X E21620 E21618 Drawout mounting E21614 E29161 Fixed or plug-in mounted C23 X X C11 C17 C22 Y R14 R15 P44 Z P43 Z Y R
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Rotary operating handles inch mm Dimensions Drawout mounting (telescopic shaft) Cut shaft at length: P38-4.80/ 122 (NSF150/250) P40-5.90/150 (NSJ400/600) E21630 E29163 L14 L13 E21628 Fixed or plug-in mounted Cut shaft at length: P38-4.96/126 (NSF150/250) P38-5.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Front accessories inch mm Extended escutcheons E21637 E21636 E21635 For toggle M D A E21655 E21654 E21653 Toggle boot M8 D3 A3 Front panel escutcheons E21643 E21641 E21642 For toggle M2 M3 A1 D1 D2 E21649 E21648 E21647 For extended escutcheon, motor operator module or rotary handle M6 M7 A2 NSF150/250N/H NSJ400/600N/H/L 40 (inch) (mm) (inch) (mm) A 3.58 91 4.84 123 A1 2.71 69 4.01 102 A2 6.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Interlocking systems inch mm Interlocking systems with rotary operating handles E28252 F E28253 Front panel cutout E28251 Dimensions J N D X M X C Y H H B A F L K G Z NSF150/250 (inch) (mm) NSJ400/600 (inch) (mm) A B C D F G H J K L M N 12.79 3.54 3.44 6.89 6.14 5.23 0.36 0.35 11.61 2.97 5.90 2.95 325 90 87.5 175 156 133 9.25 9 295 75.5 150 75 16.38 4.53 3.94 7.87 8.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Connections inch mm Fixed mounted E28255 E28254 P13 G4 X X G5 Y Z Bar connection NSF150/250 (M8 screws) Z Z 0.55 14 4.46 113.5 2.75 70 X X Cable connection NSF150/250 NSJ400/600 Z Z E28261 E28260 E28258 K1 NSJ400/600 (M10 screws) E28259 E28257 E28256 Front connections K1 Z 1.83 46.5 0.55 14 4.46 113.5 2.75 70 X NSF150/250 E28263 E28262 X 0.39 10 0.70 18 ∅0.33 ∅8.6 NSJ400/600 0.51 13 ∅0.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams inch mm K1 E28266 Plug-in or drawout mounting E28265 Connections K1 X X Z Y Rear connections P22 P23 E28268 E28267 Rear connections fitted at lower limit Z E G33 X P22 P23 E28270 E28269 Rear connections fitted at upper limit Z E G35 X NSF150/250N/H (inch) (mm) NSJ400/600N/H/L (inch) (mm) ® COMPACT NS circuit breaker E 0.15 4 0.23 6 G33 2.5 63.5 4.09 104 G35 3.16 80.5 5.07 129 K1 1.37 35 1.
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Auxiliary circuits Wiring diagrams 92 14 22 94 12 24 OF2 OF1 82 GN 24 32 34 72 VT 84 RD 32 VT VT YE 24 YE 22 14 VT GN D1 C1 94 12 YE 92 RD D1 C1 WH BK CE T1 R1 OR Z11 e+ 354 YE RD BK VT 312 352 GN 314 GY VT GY E28271 Manually-operated circuit breaker 74 82 84 OF3 CAF1 CAF2 CAO1 trip unit (3) MN (1) SDE (2) SD MX Id 21 GY 11 GY BL BL GY 91 OR C2 D4 BL RD WH S
® COMPACT NS circuit breaker: dimensions, connections and wiring diagrams Auxiliary circuits Motor operator: automatic resetting after tripping Use of the motor operator (standard wiring diagram) E28273 CN1 - CN 1 + CN2 - CN 2 – DP1 ON OFF H1 H2 82 B2 SDE OR A4 A2 B4 BL GN (1) 84 WH RD A2 A4 B4 MT trip unit A1 GN 81 BK BK (1) L1 E28275 E28274 A1 L1 ON D1 OFF A2 ON A4 B4 Motor operator + undervoltage trip C1 OFF A2 A4 B4 Motor operator + shunt trip Mandatory
® COMPACT NS circuit breaker: supplementary technical information Trip curves Trip units for COMPACT® NSF150–NSF250 circuit breakers TM20DP E28277 E28276 TM15DP 10 000 5 000 10 000 5 000 2 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 t(s) 10 t(s) 5 2 5 2 1 1 .5 .5 .2 .2 .1 .1 .05 Im = 25 x In .05 .02 .01 .005 .5 1 Im = 20 x In .02 reflex tripping : t < 10 ms 2 5 10 20 50 100 500 1000 .01 .005 .
® COMPACT NS circuit breaker: supplementary technical information Trip curves TM60DP 10 000 5 000 E28281 E28280 TM50DP 10 000 5 000 2 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 t(s) 10 t(s) 5 2 5 2 1 1 .5 .5 .2 .2 Im = 10 x In .1 .1 .05 .05 .02 .01 .005 .5 1 Im = 16 x In .02 reflex tripping : t < 10 ms 2 5 10 20 50 100 500 1000 .01 .005 .
® COMPACT NS circuit breaker: supplementary technical information Trip curves Trip units for COMPACT® NSF150–NSF250 circuit breakers TM100–225DP E28285 E28284 TM90DP 10 000 5 000 10 000 5 000 2 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 10 t(s) t(s) 5 5 2 2 1 1 .5 .5 .2 .2 Im = 11.5 x In .1 .1 .05 .05 .02 .02 .01 .005 .5 1 Im = 5…10 x In reflex tripping : t < 10 ms 2 5 10 20 50 100 500 1000 10 000 .01 .005 .
® COMPACT NS circuit breaker: supplementary technical information Trip curves Effect of high temperatures When the ambient temperature is greater than 40°C, overload protection characteristics are slightly modified. When determining tripping times using time/current curves, the Ir values corresponding to the thermal setting on the circuit breaker must be reduced using the coefficients below: 45°C 0.975 50°C 0.95 55°C 0.925 60°C 0.90 65°C 0.875 70°C 0.
® COMPACT NS circuit breaker: supplementary technical information Trip curves Trip units for COMPACT® NSJ400–NSJ600 circuit breakers STR53UP 10 000 5 000 E38878 E28297 STR23SP 2 000 1 000 10 000 5 000 2 000 1 000 Ir = 0.4–1 x In 500 500 200 100 200 100 50 50 20 10 20 I2t = ON 10 For hot start (0.9 x Ir) divide max. time by 2, min. time by 4 Isd = 1.5 5 t(s) Ir = 0.4–1 x In tr = 1–8 s (6Ir) 5 t(s) 2 1 .5 Im = 2–9 x Ir 2 1 .5 Isd = 1.5 Isd = 1.5–7 x Ir I2t = OFF .2 .2 .1 .05 .1 .
® COMPACT NS circuit breaker: supplementary technical information Trip curves Reflex tripping E28287 All COMPACT® NS circuit breakers and switches incorporate the exclusive reflex tripping system. This extremely simple system breaks very high fault currents by mechanically tripping the device via a "piston" actuated directly by the pressure produced in the breaking units resulting from a short circuit. For high short-circuit thermal withstand, this system provides a faster break.
® COMPACT NS circuit breaker: supplementary technical information Let-through curves at 480 V Maximum peak let-through current (Amperes) E28288 3 Maximum (*) Peak Let-Through Current (Amperes x 10 ) (*) Based on maximum values obtained throughout the circuit breaker development and UL test programs.
® COMPACT NS circuit breaker: supplementary technical information Let-through curves at 600 V 3 Maximum (*) Peak Let-Through Current (Amperes x 10 ) (*) Based on maximum values obtained throughout the circuit breaker development and UL test programs.
® COMPACT NS circuit breaker: supplementary technical information Current limiting curves at 380/415 V Maximum peak let-through current (Amperes) (*) Based on maximum values obtained throughout the circuit breaker development and UL test programs.
® COMPACT NS circuit breaker: supplementary technical information Current limiting curves at 690 V Maximum peak let-through current (Amperes) (*) Based on maximum values obtained throughout the circuit breaker development and UL test programs.
® COMPACT NS circuit breaker: supplementary technical information UL 489 test procedure Standard tests For electronic trip circuit breakers and uncompensated thermal-magnetic circuit breakers rated 40°C, the test sequences are as shown in the table: Test Sequence X Y Z 200% calibration at 25°C (77°F) 135% calibration at 25°C (77°F) Calibration of adjustable instantaneous trip Overload Tungsten lamp load 100% calibration at 40°C (104°F) Temperature and 100% calibration at 25°C (77°F) Endurance 200% cali
® COMPACT NS circuit breaker: supplementary technical information UL 489 test procedure Interrupting ability Dielectric Interrupting ability (Y sequence) After endurance tests and calibrations are repeated, the circuit breaker completes an opening (O) followed by a close-open operation (O-t-CO), with specified current.
® COMPACT NS circuit breaker: supplementary technical information IEC 947-2 test procedure Standard tests Consisting of seven parts, the IEC 947 Standard applies to all low-voltage equipment designed for industrial application. Three documents are to be consulted for circuit breakers and switches. ■ IEC 947-1: general regulations; ■ IEC 947-2: circuit breakers; ■ IEC 947-3: switches. Two categories of devices The IEC 947-1 standard defines two categories of devices.
® COMPACT NS circuit breaker: supplementary technical information IEC 947-2 test procedure Test sequences Sequence 1 - General characteristics Category of devices All circuit breakers 2 - Breaking capacity during operation All circuit breakers 3 - Ultimate breaking capacity (Icu) A B if Icu > Icw 4 - Admissible short duration current (Icw) B Combined sequence Icw = Ics replaces sequences 2 and 4 Icw = Ics = Icu replaces sequences 2, 3 and 4 ® COMPACT NS circuit breaker Tests - trip unit contro
® COMPACT NS circuit breaker: supplementary technical information Routine and maintenance guidelines ! DANGER Recommended inspection intervals • This equipment must be installed and serviced only by qualified electrical personnel. Merlin Gerin circuit breakers are designed to be maintenance-free. However, all equipment with moving parts requires periodic inspection to ensure optimum performance and reliability.
® COMPACT NS circuit breaker: supplementary information E28023 Catalog numbers COMPACT NSF Circuit Breaker with Thermal-Magnetic Trip Unit Rating (A) Bus Bar Connection Cable Connection NFNF36015 NFNF36020 NFNF36030 NFNF36040 NFNF36050 NFNF36060 NFNF36070 NFNF36080 NFNF36090 NFNF36100 NFNF36125 NFNF36150 NFNL36015 NFNL36020 NFNL36030 NFNL36040 NFNL36050 NFNL36060 NFNL36070 NFNL36080 NFNL36090 NFNL36100 NFNL36125 NFNL36150 NFNF36175 NFNF36200 NFNF36225 NFNF36250 NFNL36175 NFNL36200 NFNL36225 NFNL362
® COMPACT NS circuit breaker: supplementary information Catalog numbers Installation and Connection ■ For factory-installed connection accessories complete the circuit breaker catalog number by inserting the termination numbers in the appropriate block. ■ For field-installable accessories order the 5-digit catalog number. Term. No. Catalog No.
® COMPACT NS circuit breaker: supplementary information Catalog numbers E18610 E18609 E10608 Electrical Accessories 2 1 to u/au man O I push push OFF ON ■ For factory-installed accessories complete the circuit breaker catalog number by inserting the option number in the appropriate block. ■ For field-installable accessories order the 5-digit catalog number.
® COMPACT NS circuit breaker: supplementary information Catalog numbers Operating Handles Option No. Catalog No.
® COMPACT NS circuit breaker: supplementary information E29169 Catalog numbers COMPACT NSJ Circuit Breaker with STR23SP Electronic Trip Unit Rating (A) Bus Bar Connection Cable Connection NJNF36150E20 NJNF36250E20 NJNF36400E20 NJNL36150E20 NJNL36250E20 NJNL36400E20 NJNF36600E20 NJNL36600E20 NJHF36150E20 NJHF36250E20 NJHF36400E20 NJHL36150E20 NJHL36250E20 NJHL36400E20 NJHF36600E20 NJHL36600E20 NJLF36400E20 NJLL36400E20 NJLF36600E20 NJLL36600E20 NSJ400N—35 kA at 480 Vac 150 250 400 NSJ600N—
® COMPACT NS circuit breaker: supplementary information Catalog numbers Installation and Connection ■ For factory-installed connection accessories complete the circuit breaker catalog number by inserting the termination numbers in the appropriate block. ■ For field-installable accessories order the 5-digit catalog number. Term. No. Catalog No.
® COMPACT NS circuit breaker: supplementary information Catalog numbers Electrical Accessories E18610 E18609 E18608 ■ For factory-installed accessories complete the circuit breaker catalog number by inserting the option number in the appropriate block. ■ For field-installable accessories order the 5-digit catalog number.
® COMPACT NS circuit breaker: supplementary information Catalog numbers Operating Handles Option No. Catalog No.
SQUARE D and companies. are registered trademarks of Square D Company or related COMPACT, MASTERPACT and DIGIPACT are registered trademarks of Schneider Electric. Square D Company PO Box 3069, 3700 Sixth St SW Cedar Rapids IA 52406-3069 USA Field Services: 1-800-634-2003 www.squared.com RONIS and PROFALUX are trademarks of HF Security. 0615CT9901 March 1999 © 1997 - 1999 Square D - All Rights Reserved. Replaces 0623CT9701 dated 1997.