Specifications

19
COMPACT
®
NS circuit breaker
COMPACT
®
NSF250N circuit breaker
on a drawout chassis
Drawout mounting
The chassis is made up of two side plates installed on the base and two other plates
mounted on the circuit breaker.
Chassis functions
All functions of the plug-in base, plus:
Disconnected position: the power circuits are disconnected, the circuit breaker is
simply "withdrawn" and may still be operated (on, off, push-to-trip);
Circuit breaker may be locked using 1 to 3 padlocks (diameter 0.19
to 0.31
inch
(5 to 8 mm), to prevent connection;
The auxiliaries can be tested (with manual auxiliary connector).
Mounting
On a backplate, through a front panel or on rails;
Horizontally or vertically.
Accessories
Auxiliary switches for installation on the fixed part of the chassis, indicating the
"connected" and "disconnected" positions;
Toggle collar for circuit breakers with toggle through front panel, intended to
maintain the degree of protection whatever the position of the circuit breaker
(supplied with a toggle extension);
Keylock which, depending on the bolt fitted, can be used to:
prevent insertion for connection;
lock the circuit breaker in connected or disconnected position;
Telescopic shaft for extended rotary handles.
Connection of auxiliaries:
Control voltage is provided through automatic secondary disconnects in the
connected position only. See page 20 for more details.
Electrical accessories can be tested in the disconnected position with an external
wiring harness.
The drawout-mounted chassis is Listed under UL file E113555 and Certified under
CSA file LR 69561.
Connected
Removed
86025
E21282
Disconnected
Installation and connections
COMPACT
®
NS circuit breaker: functions and characteristics