Specifications

26
COMPACT
®
NS circuit breaker
COMPACT
®
NS circuit breaker: functions and characteristics
Accessories
Motor operator
COMPACT
®
NSJ400N circuit breaker with
motor operator
The motor operator remotely operates the circuit breaker featuring easy and sure
operation:
All circuit breaker indications and information remain visible and accessible,
including trip units settings and circuit breaker connection;
Suitability for isolation is maintained and padlocking remains possible;
Double insulation front face.
Applications
Local motor-driven operation, centralized operation, automatic distribution control;
Normal/standby source changeover or switching to a replacement source to
optimize energy costs;
Load shedding and reconnection to optimize energy costs;
Synchrocoupling.
Automatic operation
On and off by two impulse type or continuous control signals;
Depending on the wiring, resetting can be done locally, remotely or automatically;
Mandatory manual reset following tripping due to an electrical fault.
Manual operation
Transfer to manual mode using switch (9) with possibility of remote mode
indication;
On and off by two push buttons;
Recharging of stored-energy system by pumping the lever nine times;
Padlocking in off position.
Installation and connection
All installation (fixed, plug-in/drawout mounting) and connection capabilities are
maintained;
Connection of the motor operator module behind its front cover to a built-in
terminal block, for stranded copper wire #14 AWG/2.5 mm
2
.
Accessories for NSJ400/600
Keylock for locking in OFF position;
Operations counter, indicating the number of ON and OFF cycles. The counter
must be installed on the front of the motor operator module.
1 Contact position indicator (suitability for isolation).
2 Outgoing circuit identification labels.
3 Spring status indicator (charged, discharged).
4 Locking device (keylock) on NSJ400/600.
5 Locking device (off position) using one to three padlocks,
diameter 0.2 to 0.32 inches/5 to 8 mm, not supplied.
6 Manual spring charging handle.
7 I (ON) push button.
8 O (OFF) push button.
9 Manual/auto mode selection switch; the position of the
switch can be indicated remotely.
10 Operations counter (COMPACT
®
NSJ400/600 circuit breaker).
86012
E28037
manu
push OFF
O
2
2
1
1
push ON
I
O OFF
charged
auto
1 3
5 6
89
2
10
4
7
MERLIN GERIN
compact
NSJ 400 N
In = 400A
circuit breaker
600V
IEC947
.2
240V
480V
600V
65k
35k
25k
Ic
u
UTE VDE BS CEI UNE NEMA
50/60Hz
UL inter. ratings
RMS Sym Amps
220/240V
380/415V
85kA
45kA
Ics = 100% Icu
Uimp = 8kV
Characteristics
NSF NSJ
Response time (ms) Opening < 500
Closing < 80
Max. cycles frequency per minute 4
Control voltage (V) AC 50/60 Hz 48–60 48–60
110–130 110–130
208–277 208–277
380–480 380–415
440–480
DC 24–30 24–30
48–60 48–60
110–130 110–130
250 250
Consumption AC (VA) Opening 500
Closing 500
DC (W) Opening 500
Closing 500
Minimum operating order 700 ms
Operating voltage 85–110 % rated voltage