Startup with options MBG11A or MLG11A
Startup of Standard Design
7.7 Startup with options MBG11A or MLG11A
1. Isolate MOVIMOT
®
drive from the supply, safeguarding it against unintentional
power-up! Dangerous voltages may still be present for up to 1 minute after
shutdown!
2. Review correct connection of MOVIMOT
®
(see the section "Electrical Installa-
tion").
3. Set DIP switch S1/1 (on MOVIMOT
®
) to ON (= address 1).
4. Set the minimum frequency f
min
with switch f2.
5. Set the ramp time with switch t1 (ramp times in relation to a setpoint step change of
50 Hz).
6. Check whether the required direction of rotation is enabled.
05064AXX
Switch f2
Detent position 012345678910
Minimum frequency f
min
[Hz]
2 5 7 1012152025303540
Switch t1
Detent position 012345678910
Ramp time t1 [s] 0.10.20.30.50.71235710
Terminal R Terminal L Message
Activated Activated Both directions of rotation are enabled
Activated Not activated Only clockwise direction of rotation is enabled
Preselected setpoints for counterclockwise rotation result in
standstill of drive
Not activated Activated Only counterclockwise direction of rotation is enabled
Setpoint selections for clockwise lead to the drive being
stopped
Not activated Not activated Unit is blocked or the drive is stopped