Startup with options MBG11A or MLG11A
Startup of Standard Design
7.7 Startup with options MBG11A or MLG11A
1. Isolate MOVIMOT
®
drive from the supply, safeguarding it against unintentional
power-up! Dangerous voltages may still be present for up to 1 minute after
shutdown!
2. Review correct connection of MOVIMOT
®
(see the section "Electrical Installa-
tion").
3. Set DIP switch S1/1 (on MOVIMOT
®
) to ON (= address 1).
4. Set the minimum frequency f
min
with switch f2.
5. Set the ramp time with switch t1 (ramp times in relation to a setpoint step change of
50 Hz).
6. Check whether the required direction of rotation is enabled.
05064AXX
Switch f2
Detent position 012345678910
Minimum frequency f
min
[Hz]
2 5 7 1012152025303540
Switch t1
Detent position 012345678910
Ramp time t1 [s] 0.10.20.30.50.71235710
Terminal R Terminal L Message
Activated Activated • Both directions of rotation are enabled
Activated Not activated • Only clockwise direction of rotation is enabled
• Preselected setpoints for counterclockwise rotation result in
standstill of drive
Not activated Activated • Only counterclockwise direction of rotation is enabled
• Setpoint selections for clockwise lead to the drive being
stopped
Not activated Not activated • Unit is blocked or the drive is stopped