Operating Instructions – MOVIMOT® MM03C - MM3XC
8
Description of the DIP switches S4
Startup with Integrated AS-Interface
8.4 Description of the DIP switches S4
DIP switch S4/1
Control process
DIP switches S4/1 = OFF: VFC operation for 4-pole motors
DIP switches S4/1 = ON: U/f operation reserved for special cases
DIP switch S4/2
Speed monitoring
Speed monitoring (S4/2 = "ON") is used for the protection of the drive during block-
ing.
If the drive is operated at the current limit for more than 1 second with active speed
monitoring (S4/2 = "ON"), the speed monitoring trips. MOVIMOT
®
signals a fault via
status LED (red, flashing slowly, fault code 08). The current limit must be attained un-
interruptedly for the duration of the delay time before the monitoring function
responds.
DIP switches
S4/3 to S4/6
Selection of options
Special functions can be selected using the binary coding of the DIP switches.
The possible values can be set as follows:
An overview of the selectable special functions can be found on page 58.
Decimal
value
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
S4/3
X X X X X X X X
S4/4 ––
X X ––X X ––X X ––X X
S4/5 ––––
X X X X ––––X X X X
S4/6 ––––––––
X X X X X X X X
X = ON
–= OFF