Operation Manual
MI 3309 BT DeltaGT Technical specifications
17
3 Technical specifications
3.1 Earth continuity
Range Resolution Accuracy
0.00 19.99 0.01 (5 % of reading + 3 digits)
20.0 199.9 0.1
Indication only
200 1999 1
Powered by ............................... battery or mains
Test currents ............................. 200 mA into 2.00
Open circuit voltage .................. <9 V AC
Pass levels ................................ 0.10 , 0.20 , 0.30 , 0.40 , 0.50 , 0.60 , 0.70 ,
0.80 , 0.90 , 1.00 , 1.50 , 2.00
Test duration ............................. 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s
Test method .............................. 2-wire measurement
Test terminals ........................... PE (Test socket) ↔ S/EB (probe)
PE (IEC Cord) ↔ PE (Test socket)
PE (terminal) ↔ S/EB (probe) (for fixed installed
appliances)
3.2 Insulation resistance, Insulation – P resistance
Range Resolution Accuracy
0.00 M 19.99 M 0.01 M
(5 % of reading + 3 digits)
20.0 M 49.9 M 0.1 M
50.0 M 199.9 M 0.1 M
Indication only
Powered by ............................... battery or mains
Nominal voltages ...................... 250 V DC, 500 V DC (- 0 %, + 10 %)
Measuring current ..................... min. 1 mA at 250 k (250 V), 500 k (500 V)
Short circuit current ................... max. 2.0 mA
Pass levels ................................ 0.01 M, 0.10 M, 0.25 M, 0.30 M, 0.50 M, 1 M, 2
M, 4 M, 7 M, 10 M, --- M
Test duration ............................. 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s
Test terminals (Insulation) ......... LN (Test socket) ↔ PE (Test socket)
LN (terminal) ↔ PE (terminal) (for fixed installed
appliances)
LN (Test socket) ↔ S/EB (probe)
LN (terminal) ↔ S/EB (probe) (for fixed installed
appliances)
Test terminals (Insulation-P) ..... LN (Test socket) ↔ S/EB (probe)