Operation Manual
MI 3309 BT DeltaGT Single test
34
LIMIT
Maximum resistance [0.10 0.20 0.30 0.40 0.50 0.60
0.70 0.80 0.90 1.00 2.00]
TIME Measuring time [2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s (continuous
measurement)]
Typical test circuits for Earth continuity resistance measurement
Figure 5.5: Measurement of Earth continuity
Figure 5.6: Measurement of Earth continuity of fixed installed DUTs of Class I
Earth continuity resistance measurement procedure
Select the EARTH CONT. function.
Set the test parameters.
Connect device under test to the instrument (see Figure 5.5 and Figure 5.6).
Press the TEST key for measurement. To stop continuous measurement press
TEST key once again.
Store the result by pressing MEM key (optional).