Operation Manual
MI 3309 BT DeltaGT Single test
47
5.2.10 (P)RCD test
The purpose of this test is to ensure the proper operation of residual current devices
(RCD) built into appliances / installations and portable residual current devices (PRCD).
Trip-out time measurement verifies the sensitivity of a (P)RCD at selected residual
currents.
The RCD test is performed via the instrument mains supply input.
Figure 5.34: (P)RCD single and auto test menus
Test parameters for (P)RCD test
Test Test function [RCD, PRCD]
I
N
Rated residual current [10 mA, 15 mA, 30 mA]
Mul
Test current multiplier I
N
[x ½, x 1, x 5]
Mod
(P)RCD test mode [(0, 180, (0,180), AUTO]
Figure 5.35: (P)RCD test current starting polarities 0, 180
Test circuits for testing RCD and PRCD
a) Testing of standard RCD