Operation Manual
MI 3309 BT DeltaGT Single test
48
b) Testing of PRCD via mains socket
c) Testing of PRCD via test socket
Figure 5.36: Testing of RCD and PRCD
5.2.10.1 (P)RCD single test
In single test a fast (P)RCD test with selected test current and with one or both starting
polarities is performed.
Trip-out time measurement procedure
Measuring PRCD
Select the RCD test function.
Select test mode.
Set test parameters.
Connect tested PRCD / device to an external voltage socket. Connect the IEC cord
to the instrument’s MAINS terminal and PRCD (see Figure 5.36b).
Depending on the type of PRCD, it may be necessary to manually switch it on.
Press the TEST key to perform measurement.
If both starting polarities are selected:
Reactivate tested PRCD.
Store the result by pressing MEM key (optional).
or
Select the PRCD test function.
Select test mode.
Set test parameters.
Connect tested PRCD between test socket and IEC connector of the DeltaGT (see
Figure 5.36c), and connect instrument’s MAINS terminal to an external voltage
socket.
Depending on the type of PRCD, it may be necessary to manually switch it on.
Press the TEST key to perform measurement.
If both starting polarities are selected:
Reactivate tested PRCD.
Store the result by pressing MEM key (optional).