Operation Manual
MI 3309 BT DeltaGT Single test
52
5.2.12 Voltage TRMS
In this function the voltage across the MAINS terminal is measured continuously.
Test circuit for voltage measurement
Figure 5.41: Voltage measurement with the IEC cord
Voltage TRMS procedure
Select the VOLTAGE TRMS function.
Connect the IEC cord to the instrument’s MAINS terminal and to the external
mains socket as shown on Figure 5.41.
Store the result by pressing MEM key (optional).
Figure 5.42: Voltage TRMS test result
Displayed results:
Main result ............. Voltage
f .............................. Frequency
Warning:
Only for voltage range from 80 V to 300 V!
5.2.13 Clamp current measurement
This function enables the measurement of AC currents in a wide range from 0.1 mA up to
16 A with current clamps. Typical applications are:
- Measuring PE leakage currents through PE conductor in permanently installed
appliances,
- Measuring load currents in permanently installed appliances,
- Measuring differential leakage currents in permanently installed appliances.