Operation Manual

MI 3309 BT DeltaGT Single test
53
Figure 5.43: Clamp current menu
Test parameters for clamp current measurement
LIMIT
Maximum current [0.50 mA, 0.75 mA, 1.00 mA, 1.50 mA, 2.00 mA, 2.25 mA,
2.50 mA, 3.50 mA, 4.00 mA, 4.50 mA, 5.00 mA, 5.50 mA, 6.00 mA, 7.00 mA,
8.00 mA, 9.00 mA, 10.0 mA, 15.0 mA, --- mA]
TIME Measuring time [2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, none]
Test circuit for clamp current measurement
Figure 5.44: Measurement of clamp current
Clamp current measurement procedure
Select the CURRENT function.
Set test parameters.
Connect the current clamp to the instrument (see Figure 5.44).
Embrace wire(s) that has to be measured with the current clamp.
Press the TEST key for measurement. To stop continuous measurement press
TEST key once again.
Store the result by pressing MEM key (optional).